DPIL

Installation Instructions

DPIL Liquid Differential Pressure Sensor Installation Instructions TG200125 Issue 1/E 21/09/05

4

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route

du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof

without obligation to notify any person of such revisions or changes.

Trend Control Systems Limited

P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com

Yx
TYPE x
=?
S=5 (characterise)
Y=, E=, U=, L=, P=, I

1

to I

2

=, O

1

to O

2

=

X

INSTALLATION

(continued)

11

Configure IQ

12

IQ

ΔP = X

I Q

I Q

IQ Configuration
Manual 90-1533

or

top menu

tYpe Sensor digI/p Driver Function loGic Loop
scHedule seQnc Analog digBit Knob sWitch Time
Zone Oss User addRess intcoN calarM reView Plot
calEndar

=?

Set up sensor type

13

14

Range

Y

E

U

L

P

I

1

I

2

O

1

O

2

DPIL/0.5

2

2

0.5

0

2

4

20

0

0.5

DPIL/1

2

2

1

0

2

4

20

0

1

DPIL/2.5

2

2

2.5

0

2

4

20

0

2.5

DPIL/4

2

2

4

0

2

4

20

0

4

DPIL/6

2

2

6

0

2

4

20

0

6

DPIL/10

2

2

10

0

2

4

20

0

10

If not using SET, use the following tables for all
IQ2 series controllers of firmware version 2.1 or
greater or IQ3 controllers; for all other I Q Controllers
see Sensor Scaling Reference Card TB100521A

(current)

Connect Pressure Points

(continued)

WEEE Directive :

At the end of their useful life the packaging
and product should be disposed of via a
suitable recycling centre.

Do not dispose of with normal household waste.
Do not burn.

g

h

i

P2 -

P1+ +

-

not used
do not open

DISPOSAL

It is recommended to use SET (software tool) for
the setting of sensor type modules.
For all IQ2 series controllers with firmware version
2.1 or greater, or IQ3 series controllers, the
following unique sensor references should be used:
DPIL/0.5:

Pressure I 0.5bar

DPIL/1: Pressure I 1bar
DPIL/2.5:

Pressure I 2.5bar

DPIL/4: Pressure I 4bar
DPIL/6: Pressire I 6bar
DPIL/10:

Pressure I 10bar

Test System