Weee directive, Installation, Disposal – TREND PIl3 User Manual

Page 4: Pil3 installation instructions, Set up iq sensor type

background image

Pressure sensor

Yx

TYPE n

:

=?

S = 5 (characterise)

Y=, E=, U=, L=, P=, I1=, I2=, O1=, O2=,

X

Set up IQ sensor type

14

tYpe Sensor digI/P Driver Function loGic Loop

scHedule seQnc

Analog digBit Knob sWitch TimeZone Oss

User addRess intcoN calarM reView Plot calEndar

=?

InstallatIon

(continued)

It is recommended to use SET (software Tool) for the setting of the sensor type module. For

all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the

appropriate SET Unique Sensor Reference from those given below should be used:

PIL3/4:

Pressure I 4 bar

PIL3/6:

Pressure I 6 bar

PIL3/10:

Pressure I 10 bar

PIL3/16:

Pressure I 16 bar

PIL3/25:

Pressure I 25 bar

Alternatively enter scaling manually as defined in table below:

For all other IQ controllers see the Sensor Scaling Reference Card TB100521A.

Y

E

U

L

P

I

1

I

2

O

1

O

2

PIL3/4 2 (current)

2

4.1

0

2

4

20

0

4

PIL3/6 2 (current)

2

6.1

0

2

4

20

0

6

PIL3/10 2 (current)

2

10.1

0

2

4

20

0

10

PIL3/16 2 (current)

2

16.1

0

2

4

20

0

16

PIL3/25 2 (current)

3

25.1

0

2

4

20

0

25

IQ

P = X

15

WEEE Directive :

At the end of their useful life the packaging and product, should

be disposed of by a suitable recycling centre.

Do not dispose of with normal household waste. Do not burn.

DIsPosal

4

PIL3 Pressure Sensor (Liquid) Installation Instructions TG200127 Issue 4, 18/02/2009

PIl3

Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2009 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls

Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation

to notify any person of such revisions or changes.

Trend Control Systems Limited

P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com

Trend Control System USA

6670 185

th

Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-controls.com