beautypg.com

Installation instructions srmac installation, Wire module to controller, Ensure plant supply is switched off – TREND SRMAC User Manual

Page 3: Connect relay to plant item

background image

SRMAC Single Relay Module (24 Vac) Installation Instructions TG101985 Issue 2/B 21/04/05

3

Installation Instructions

SRMAC

INSTALLATION

(continued)

Wire module to controller

6

Ensure Plant Supply is Switched off

7

O

I

SRMAC

Plant

Supply

Supply

WARNING: The wires may be connected

to hazardous voltages.
Disconnect power before
attempting any wiring.

Relay Output Arc
Suppression Installation
Instructions TG200208

IQ

SRMAC

24 V

OUT

A2

A1

Relay
coil

polarity independent

I

= 31.6 mA

A2

coil

A1

NO

14

N

C

12

11

C

O

Connect Relay to Plant Item

8

use either normally open or
normally closed contact

Supply

Plant

item

14

C

SRMAC

NO

NC

12

A2

coil

A1

NO

14

N

C

12

11

C

O

Terminal size 2 x 2.5 mm

2

(11 AWG) wires

Arc suppression
recommended

Terminal size 2 x 2.5 mm

2

(11 AWG) wires

250 Vac @ 10 A (resistive), 5 A
(inductive, cos ø>=0.4)
20 Vdc @ 8 A (resistive)
24 Vdc @ 2 A (inductive, T<=30 ms)

triac output

11