Connect module to hvac equipment, Close panel, Switch on iq – TREND 2SRM (24 Vac_dc) User Manual

Page 3: Continued), 14 to 20 awg) supply c no nc, 2srm, Iq hvac equipment 1

background image

2SRM (24 Vac/dc) Installation Instructions TG103210 Issue 2 07/07/08

3

Installation Instructions

2SRM (24 Vac/dc)

3

Installation

(continued)

Ensure HVAC Equipment Power
Supplies are Switched off

8

O

I

O

I

2SRM

HVAC

Equipment

2

Supply

WARNING: The wires may be connected

to hazardous voltages.
Disconnect power before
attempting any wiring.

Arc suppression
recommended

Relay Output Arc
Suppression Installation
Instructions TG200208

Terminal size 0.5 to 2.5 mm

2

(14 to 20 AWG)

Supply

C

NO
NC

Connect module to HVAC

equipment

9

0V

24

V

AUTO ON OFF AUTO ON OFF

J1

J2

LO

W

/LO

W

E

R

HIGH/RAISE

NC NO C NC NO C

IN

2

IN

1

RL1

RL2

2SRM

C

NO
NC

C

NO
NC

Supply

C

NO
NC

Supply

Channel 2

OUT

Channel 1

OUT

Channel 2
OUT

Channel 1
OUT

HVAC

Equip-

ment

2

Contacts rated 5 A max. at 240 Vac single
phase only (Cosø>=0.4), and 30 Vdc (resistive
load). 2 A for 24 Vdc (inductive load,
T<=30ms).

Close panel

10

Switch on IQ

11

IN 0V

24

V

AUTO ON OFF AUTO ON OFF

J1

J2

LOW/LOWER

HIGH/R

AISE

NO NC C

NO NC C

IN

2

1

2

3

4

5

6

7

8

9

1 0

A

B

C

D

D P

T X

R X

O K

L A N

1

2

3

4

5

6

7

8

9

1 0

1 1

1 2

1 3

1 4

1 5

V

2 4 V

1 6

1 7

1 8

1 9

2 0

O

I

IQ

HVAC

Equipment

1

HVAC

Equip-

ment

1