Iq3xact installation instructions, 4 installation - configuration, Connect supervisors/tools/display panels – TREND IQ3xact User Manual
Page 12

12
IQ3xact Web Enabled Controller Installation Instructions TG200766 Issue 2 21/04/08
IQ3xact
Installation Instructions
963 v2.1, SET v6.2, 916, IQView
• Connect using virtual CNC in IQ3 or 3xtend/EINC L (IQView
can use its integral vCNC).
• Virtual CNC must be set up in IQ3 or 3xtend/EINC L (or IQView).
• PC must be set up for IP addressing (use host name if automatic
addressing being used).
• Software must be set up with IP address (or host name if
automatic addressing being used) of virtual CNC and CNC port
number.
• PC and virtual CNC must be on same subnet (same subnet mask).
• Software talks to IQ3 Lan No, Oustation address using vCNC.
Web Browser (Internet Explorer v6)
• PC must be set up for IP addressing.
• PC and IQ3 must be on same subnet (same subnet mask).
Ethernet, Remote Subnet (across Routers)
963 v2.1, SET v6.2, 916, IQView
Set up as adjacent except
• Set up default router in PC and IQ3.
• PC and IQ3 are on different subnets.
• WINS server(s) must be set up if host names being used
across routers.
Ethernet, Local Subnet
Router
IQ3
Router
Ethernet
IQView
963 v2.1, SET v6.2, 916
IQ3/LAN
current loop
Lan
Router
IQ3
Router
Ethernet
Current loop (IQ3/LAN only)
IQView
Web Browser (Internet Explorer v6)
Set up as adjacent except
• Set up default router in PC and IQ3.
• PC and IQ3 are on different subnets.
• WINS server(s) must be set up if host names being used
across routers.
• Browser talks to IQ3 IP address (or host name if automatic
addressing being used).
• For Windows XP SP1, download the Sun Java runtime
environment v1.4 (or greater) from Java.com
100-240 V
OK RX
Connect Supervisors/Tools/Display Panels
RS232 Local Supervisor
963 v2.1, SET v6.2, 916, IQView
• Trend text comms only, no upload/download (e.g. SET live
edit only).
• Use Lan No, Outstation address.
• Set local supervisor port address to non-zero for network
access
RJ11
or
or
RD-IQ,
SDU-xcite
IQView
RD-IQ, SDU-xcite
PC (963 v2.1, SET v6.2, 916)
CABLE/EJ105650
RD/SDU-IQ3COMMSCABLE/3M
RD/SDU-IQ3COMMSCABLE/10M
CABLE/EJ101422
RJ11
RJ11
RJ11
RJ11
RJ11
9 Way D type
female
IQ3
IQ3
IQ3
SDU-xcite, RD-IQ
• Set local supervisor port address to zero
• For RD-IQ, strategy must use particular strategy items (see
step 22)
963 v2.1, SET v6.2,
916
26
4 Installation - Configuration