IQ3xact Web Enabled Controller Installation Instructions TG200766 Issue 2 21/04/08

IQ3xact

Installation Instructions

963 v2.1, SET v6.2, 916, IQView
• Connect using virtual CNC in IQ3 or 3xtend/EINC L (IQView
can use its integral vCNC).
• Virtual CNC must be set up in IQ3 or 3xtend/EINC L (or IQView).
• PC must be set up for IP addressing (use host name if automatic
addressing being used).
• Software must be set up with IP address (or host name if
automatic addressing being used) of virtual CNC and CNC port
number.
• PC and virtual CNC must be on same subnet (same subnet mask).
• Software talks to IQ3 Lan No, Oustation address using vCNC.

Web Browser (Internet Explorer v6)
• PC must be set up for IP addressing.
• PC and IQ3 must be on same subnet (same subnet mask).

Ethernet, Remote Subnet (across Routers)

963 v2.1, SET v6.2, 916, IQView
Set up as adjacent except
• Set up default router in PC and IQ3.
• PC and IQ3 are on different subnets.
• WINS server(s) must be set up if host names being used
across routers.

Ethernet, Local Subnet

Router

IQ3

Router

Ethernet

IQView

963 v2.1, SET v6.2, 916

IQ3/LAN

current loop

Lan

Router

IQ3

Router

Ethernet

Current loop (IQ3/LAN only)

IQView

Web Browser (Internet Explorer v6)
Set up as adjacent except
• Set up default router in PC and IQ3.
• PC and IQ3 are on different subnets.
• WINS server(s) must be set up if host names being used
across routers.

• Browser talks to IQ3 IP address (or host name if automatic
addressing being used).
• For Windows XP SP1, download the Sun Java runtime
environment v1.4 (or greater) from Java.com

100-240 V

OK RX

Connect Supervisors/Tools/Display Panels

RS232 Local Supervisor

963 v2.1, SET v6.2, 916, IQView
• Trend text comms only, no upload/download (e.g. SET live
edit only).
• Use Lan No, Outstation address.
• Set local supervisor port address to non-zero for network
access

RJ11

or

or

RD-IQ,

SDU-xcite

IQView

RD-IQ, SDU-xcite

PC (963 v2.1, SET v6.2, 916)

CABLE/EJ105650

RD/SDU-IQ3COMMSCABLE/3M
RD/SDU-IQ3COMMSCABLE/10M

CABLE/EJ101422

RJ11

RJ11

RJ11

RJ11

RJ11

9 Way D type
female

IQ3

IQ3

IQ3

SDU-xcite, RD-IQ
• Set local supervisor port address to zero
• For RD-IQ, strategy must use particular strategy items (see
step 22)

963 v2.1, SET v6.2,

916