Installation instructions nbox/xnc220, 2 installation - configuration, Set the network address – TREND NBOX_XNC220 User Manual
Page 5: Close flap, Disconnect i/o, Open flap, Set the network baud rate

5
NBOX/XNC220 Installation Instructions TG200019 Issue 1/E 14/11/06
Installation Instructions
NBOX/XNC220
/
/
/
1
2
8
4
1
6
3
2
6
4
1
K
2
9
K
6
1
9
K
2
B A U D
A D D R E S S
O N
Set the Network Address
8
1 2 3 4 5 6 7 8 9 10
A
B
C
D
TX
RX
OK
1
2
SET
NOT SET
Address
= A
address
1, 4 to 9, 11 to 119
0, 2, 3, 10 or >119
e.g.
Address = 2 + 16 = 18
= A and
= A
or
= A
or
= A
or
NBOX/XNC220
* Note that a second address on the network is used by Comport
(default COM port 2 uses address switch setting +1). It can be
set up by software for communication to the TCL part
9
Close Flap
A+1
A+1
A+1
A+1*
Disconnect I/O
6
Open Flap
5
WARNING:
Removal of the cover exposes
dangerous voltages.
417-IEC-5036
1
2
8
4
1
6
3
2
6
4
1
K
2
9
K
6
1
9
K
2
B A U D
A D D R E S S
O N
Set the Network Baud Rate
7
1 2 3 4 5 6 7 8 9 10
A
B
C
D
TX
RX
OK
1
2
1
K
2
9
K
6
1
9
K
2
1
K
2
9
K
6
1
9
K
2
1
K
2
9
K
6
1
9
K
2
= 19k2 baud
= 9k6 baud
= 1k2 baud
Trend Baud Rate
= B
= B
= B
= B
= B
3.2 Installation - Configuration