beautypg.com

System Sensor RR1 User Manual

Page 4

background image

Three-Year Limited Warranty

System Sensor warrants its enclosed relay module to be free from defects
in materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for this relay module. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter the obliga-
tions or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
relay module which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-

ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.

M500-12-00

4

I56-1168-02

© System Sensor 1998

Minimum Conditions Required for Proper Operation of the RR1 Upon Fire Alarm

For 2-Wire Model Smoke Detectors (Model 2100AT)
Auxiliary power supply for smoke detector sounders upon alarm and one of the following:
1.

Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required

–or–

2.

Auxiliary power supply for RR1 and auxiliary relay with normally open contact activated by fire alarm only

For 4-Wire Model Smoke Detectors (Models 2112/24AT, 2112/24ATR, 2112/24AITR)
1.

Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required

–or–

2.

Auxiliary relay with normally open contact activated by fire alarm only

NOTE: Outputs must be continuous (non-coded, non-pulsed.) The RR1 will not function properly in panels that provide
only single combined burglary and fire alarm output unless the minimum conditions noted above are present.