System Sensor CZ-6 User Manual
Page 4

0
1
2
3
4
5 6
7 8 9
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
A2143-10
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
+
–
+
–
T6
T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
EXTERNAL
SUPPL
Y
0
1
2
3
4
5 6
7 8 9
POWER-LIMITED
AND SUPERVISED
1. To use a common power supply between multiple CZ-6 mod-
ules, connect a long power supply jumper from T5 or T6 to T5
or T6 on the adjacent CZ-6 module.
1. To select Class A, remove the two shunts from the
“A/B select” positions.
2. To use a common power supply between multiple CZ-6 mod-
ules, connect a long power supply jumper from T5 or T6 to T5
or T6 on the adjacent CZ-6 module.
0
1
2
3
4
5 6
7 8 9
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IN
OUT
+0
+1
+2
+3
+4
+5
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6
T5
IDC 2
IDC 3
(–)
(+)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
EXTERNAL
SUPPL
Y
0
1
2
3
4
5 6
7 8 9
POWER-LIMITED
AND SUPERVISED
+
–
+
–
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
Figure 7. Interface two-wire conventional detectors – Class B, Style B:
Figure 8. Interface two-wire conventional detectors – Class A, Style D.:
D500-49-00
4
I56-1799-005
C0240-01
C0241-01