System Sensor RR2 User Manual
Page 3

D500-44-00 3 I56-1683-02
S0127-00
Figure 4. 4-Wire system triggered from alarm relay contact:
EOL
+
+
–
A
A
UL LISTED
ALARM
CONTROL
PANEL
DETECTOR
POWER
+
–
+
–
AUX POWER
OR
DETECTOR
POWER
Power
INITIATING
CIRCUIT
+
–
+
+
–
Power
ALARM
RELAY
(NO Contact)
NC
NO
C
Aux
A
A
NC
NO
C
Aux
EOL RELAY
(shown energized)
PURPLE
T+
YELLOW
IN+
ORANGE
IN–
RED
PWR+
BLACK
PWR–
BROWN
OUT+
WHITE
OUT–
S0128-00
Figure 5. Connecting 2100AT smoke detectors to Ademco controls using RR2 module triggered from
bell/alarm circuit:
EOL
2K OHMS
+
+
–
A
+
RA400Z
A
-
+
–
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
2-WIRE
SMOKE
ZONE
PURPLE
T+
+
–
+
–
AUX POWER
YELLOW
ORANGE
RED
BLACK
BROWN
WHITE
Power
Not
Used
+
+
–
A
+
RA400Z
A
-
+
–
Power
Not
Used
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
VISTA-20
VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
SYSTEM SENSOR
POWER REVERSAL
RELAY MODULE (RR2)
(MOUNT INSIDE CONTROL ENCLOSURE)
470
Ω
1/2 WATT
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
S0129-00
Figure 6. Connecting 2100AT smoke detectors to Ademco controls using RR2 module triggered from
auxiliary relay:
EOLR
2K OHMS
+
+
–
A
+
RA400Z
A
-
+
–
AUXILIARY
RELAY
2-WIRE
SMOKE
ZONE
+
–
+
–
YELLOW
ORANGE
RED
BLACK
BROWN
WHITE
Power
Not
Used
+
+
–
A
+
RA400Z
A
-
+
–
Power
Not
Used
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
5110XM
5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
SYSTEM SENSOR
POWER REVERSAL
RELAY MODULE (RR2)
(MOUNT INSIDE CONTROL ENCLOSURE)
470
Ω
1/2 WATT
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
AUXILIARY
POWER
OUTPUT
N.C.
N.O.
NOT REQUIRED ON 5110XM
WHEN 5100XM JUMPER W3 INTACT
TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY
Connection Diagrams with Ademco Vista Panels
The connection diagrams enclosed show how to connect the 2100AT model smoke detector to the Vista panels using the
System Sensor power reversal relay module (RR2). Please make sure that the smoke detectors are connected properly to
the zones specified in the wiring diagrams for proper operation of the smoke detectors.
Programming information:
• The supervisory feature for the
bell circuit must be turned off.
See applicable control manual
for procedure.
RR2 Configuration:
•Set switch on RR2 to “OFF”.
Programming information:
• Program Auxiliary relay to
activate on alarms
• Assign Auxiliary relay as an
output for zones programmed
for fire alarm response only
(Types 9, 16, or 17)
RR2 Configuration:
• Set switch on RR2 to “ON”.