beautypg.com

System Sensor 2551HR Plug-in Intelligent User Manual

System Sensor Equipment

background image

D500-41-00

1

I56-1437-00

2551HR Plug-in Intelligent

Photoelectronic Sensors

with Communications

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
Please thoroughly read the system wiring and installation
manual, which provides detailed information on sensor
spacing, placement, zoning, and special applications. Cop-
ies of these manuals are available from System Sensor.

NOTICE: This manual should be left with the owner/user
of this equipment.

IMPORTANT: These detectors must be tested and main-
tained regularly following NFPA 72 requirements. These
detectors should be cleaned at least once a year.

General Description
The model 2551HR photoelectronic sensors utilize a state-
of-the-art, optical sensing chamber. These sensors are de-
signed for use with duct housings DH500 and DH500AC/
DC only, and to be used with compatible control panels
only. Connect detectors only to compatible control units.
(For installation in Canada, refer to CAN/ULC-S524-M86,
Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)

Two LEDs on each sensor light to provide a local 360

°

vis-

ibility of the sensor indication. The LEDs can be latched
ON by code command from the panel for an alarm indica-
tion. The LEDs can also be unlatched to the normal condi-
tion by code command. Remote LED annunciator

Specifications

Diameter:

6.1 inches (15.5 cm) installed in B501B
4.0 inches (10.2 cm) installed in B501

Height:

3.2 inches (8.1 cm)
Add 0.5 inches (1.3 cm) for thermal models

Weight:

9.6 ounces (272 g)

Installation Temperature Range

2551: 32

°

to 120

°

F (0

°

to 49

°

C)

2551T: 32

°

to 100

°

F (0

°

to 38

°

C)

Installation Humidity Range:

10% to 93% Relative Humidity

Mounting:

B501B flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit

Maximum Air Velocity:

3000 Ft./Min. (15 m/S)

Voltage Range:

15 to 32 Volts DC Peak

Standby Current:

230

µ

A @ 24 VDC

LED Current:

6.5 mA @ 24 VDC

capability is available as an optional accessory (part no.
RA400Z).

Wiring Guide
Refer to the installation instructions for the particular plug-
in base being used: 1) for the B501B base (D550-01-01); 2)
for the B501 base (D550-02-00); 3) for the RMK400 used
with the B501 base (D450-07-00). Bases are provided with
screw terminals for power, ground, and remote annunciator
connections (see Figure 1).

NOTE: All wiring must conform to applicable local codes,

ordinances, and regulations.

NOTE: Verify that all sensor bases are installed and that

the wiring polarity is correct at each base.

WARNING

Remove power from the loop before installing sensors.

1. Install sensors:

a. Verify that the sensor type matches the type written

on the label on the base.

b. Set the sensor to a desired address and then write the

address on the label on the base.

c. Place the sensor into the sensor base.