beautypg.com

Altitude correction and tema (on/off), Standard and non-standard settings, Select a preset – System Sensor CD100VC User Manual

Page 2: For custom settings, Software operation

background image

Altitude Correction and TEMA (On/Off)

1. Press

+

and hold (at least 5 seconds) until the sensor enters the

edit mode.

2. The first menu will be the Altitude correction. The adjustments will in-

crease/decrease in 500 ft. increments. To do this use the Up/Down Rocker
Button to adjust to the proper altitude.

3. Press

to lock in value then press

to proceed to TEMA.

4. Use the Up/Down Rocker Button to switch to On or Off.

5. Press

to lock in value then press

to proceed to Normal Mode.

Note: It is recommended that the TEMA feature is left on for the best
sensor operation.

Standard and Non-Standard Settings

The Non-Standard settings can be changed at any time after the sensor is
powered up. These settings have 7 variables and follow in sequence with the
Preset/Variable chart (see reverse side of this sheet). The Altitude and TEMA
feature can be changed without entering into the Non-Standard mode.
The Standard Settings (see reverse side of this sheet) are factory set and
cannot be changed. Like the Non-Standard settings, Altitude and TEMA can be
changed.

Select a Preset

(from the STDSET Menu)

1. Press

+

and hold (at least 5 seconds) until the sensor enters the

edit mode.

2. Press

2 times. You will enter the

“STDSET” Menu.

3. Use the Up/Down Rocker Button to select the Preset number. Use the

“Preset” chart (on reverse side of this sheet) to select the desired
“Variables”.

4. Press

to lock in selection then press

to return to monitoring mode.

For Custom Settings

(from the NONSTD Menu)

1. Press

+

and hold (at least 5 seconds) until the sensor enters the

edit mode.

2. Press

2 times. You will enter the

“STDSET” Menu.

3. Use the Up/Down Rocker Button to toggle to the “NONSTD” Menu and

press

.

4. Use the Up/Down Rocker Button to scroll through the 8 variables. The

variables begin with customizing the ppm levels and end with hysterisis.

5. Press

to move through variables. Use the Up/Down Rocker to toggle to

desired setting.

6. Press

to lock in selection then press

to continue to next Variable.

Software Operation

Your new Innovair™ CD100VC CO

2

Ventilation Controller uses state-of-the-art

dual beam Absorption Infrared™ Technology. This patented technology
provides a stable, accurate and reliable sensor.
The sensor is also equipped with Engelhard Sensor Technologies’ patented
TEMA (Time Extended Measurement Algorithm) software. The TEMA software
will automatically sense and adjust for any sensor drift minimizing calibration
frequency to once every five years.
The Ventilation Controller is shipped with 9 preset settings (named Standard
Sets) and one setting for customizing (named Non-Standard). Two additional
settings are available; altitude adjustments and TEMA (on/off). These two are
accessible without entering the Standard or Non-Standard settings.