American Power Conversion MX28B-400 User Manual

Page 40

background image

MX28B-400 +24V Product Manual

34

990-9218

(

Table 6.4-1. Parameter Locations, Descriptions, and Default Values)

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Output Relay Alarms

Output Relay 1 {1}

[SYSTEM/OUT-RLY/RLY-MAP]

Output Relay 1 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).

Out-Rly 1 Alm m+

Ignore







Output Relay 6 {1}

[SYSTEM/OUT-RLY/RLY-MAP]

Output Relay 6 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).

Out-Rly 6 Alm m+

Ignore

LVD SETUP

LVD1 Trip {1}

[MODULES/LVD/PARAM]

LVD trip (disconnect) threshold voltage.

LVD1 Trip

m+

21.00 V

LVD1 Restore {1}

[MODULES/LVD/PARAM]

LVD restore (reconnect) threshold voltage.

LVD1 Reset

m+

24.00 V

LVD1 Option {1}

[MODULES/LVD/SET-ALM]

Set to “Enable” if the unit has an LVD.

LVD1

Option

m+

Enable

LVD2 Trip {1}

[MODULES/LVD/PARAM]

LVD trip (disconnect) threshold voltage.

LVD2 Trip

m+

21.00 V

LVD2 Restore {1}

[MODULES/LVD/PARAM]

LVD restore (reconnect) threshold voltage.

LVD2 Reset

m+

24.00 V

LVD2 Option {1}

[MODULES/LVD/SET-ALM]

Set to “Enable” if the unit has an LVD.

LVD2

Option

m+

Enable

LVD

Alarm

LVD1 Alarm {1}

[MODULES/LVD/SET-ALM]

Sets the priority or “mapping” of an LVD Alarm.

LVD1 Open Alm m+

Minor

LVD2 Alarm {1}

[MODULES/LVD/SET-ALM]

Sets the priority or “mapping” of an LVD Alarm.

LVD2 Open Alm m+

Minor