Power output capacity, Rectifiers, Control unit – American Power Conversion MX28B-400 User Manual
Page 17: Ac input power, Ower, Utput, Apacity, Ectifiers, Ontrol, Ac i
MX28B-400 +24V Product Manual
990-9218
11
4.2 Power Output Capacity
The power supplies a maximum of 400 amps or 300 amps with N+1 redundancy. The housing
for this configuration provides space for one rectifier shelf that can hold up to four rectifiers, a
control unit, and one tier of up to 24 distribution circuit breakers.
4.3 Rectifiers
The rectifiers are APC DC Network Solutions Inc. Model MRF28H27BV with specifications as
follows:
•
= Input Voltage:
176-264V ac (230V ac nominal) @ 45-66 Hz
•
= Input Current per Rectifier:
13.9 Amps @ 230V ac
•
= Apparent Power Factor:
99% Typical, 98% Minimum
•
= Output Voltage:
27.2 V dc
•
= Over-voltage Protection:
Set at 31.5 V dc
•
= Output Current per Rectifier:
100A Maximum, Continuous
•
= Power Output per Rectifier:
2800W Continuous, Vin > 198V ac
•
= Efficiency:
89%
Typical
•
= Cooling:
Fan cooled, front to rear airflow
•
= Ambient Temperature:
-25°C to 65°C Operational
4.4 Control Unit
The microprocessor-based power system control unit is 1U high (1.75”) and provides control
and monitoring functions. Features implemented are:
•
= 32-character alphanumeric display
•
= LED alarm and status indicators
•
= Standard voltage and battery charging control
•
= Battery temperature compensation (optional)
•
= Monitoring of up to two shelves of four rectifiers each
•
= Individual alarm monitoring of 24 breakers
•
= Eight alarm / annunciation relays (Major, Minor, and six user defined) with form C contact
outputs
•
= Four external alarm inputs (either N.O. or N.C. contacts)
•
= Control of either a battery or a load LVD
4.5 AC Input Power
Each rectifier requires 208/220/240V ac, single-phase, 50/60 Hz, supplied through an external
20-amp two-pole breaker. A rear located enclosure, with two holes for customer-supplied one-
inch conduit entry, provides a terminal strip(s) for ac input power connection and a separate
“Earth Ground” bar for connection of the safety ground wire(s).