MX28B-400 +24V Product Manual
990-9218
33
(
Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER
DESCRIPTION
DISPLAY SCREENS /
DEFAULT SETTINGS
INPUT RELAY SETUP
Input Relay 1 Alias {1}
[SYSTEM/IN-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
In-Rly 1
m+
Input Relay 1
•
•
•
•
•
•
•
•
•
Input Relay 4 Alias {1}
[SYSTEM/IN-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
In-Rly 4
m+
Input Relay 4
Input Relay Alarms
Input Relay 1 {1}
[SYSTEM/IN-RLY/RLY-MAP]
An alarm activated in response to an external contact closure
or opening at the Input Relay 1 connection.
In-Rly 1 Alm
m+
Ignore
•
•
•
•
•
•
•
•
•
Input Relay 4 {1}
[SYSTEM/IN-RLY/RLY-MAP]
An alarm activated in response to an external contact closure
or opening at the Input Relay 4 connection.
In-Rly 4 Alm
m+
Ignore
OUTPUT RELAY SETUP
Output Relay 1 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Out-Rly 1
m+
Relay 1
•
•
•
•
•
•
•
•
•
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Out-Rly 6
m+
Relay 6
Output Relay Minor Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Relay Minor
m+
Minor
Output Relay Major Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Relay Major
m+
Major
Output Relay 1 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 1 Dly m+
0 sec
•
•
•
•
•
•
•
•
•
Output Relay 6 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 6 Dly m+
0 sec