Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

4

UTS Specifications

UTS6/UTS6H

UTS6BI

UTS10BI

Output

Nominal voltage

120 V circuits

120 V six total

120 V four total

120 V eight total

Nominal voltage

240 V circuits

N/A

240 V

one across Phase A & B

240 V

one across Phase A & B

Current per circuit

20 A maximum

20 A maximum

20 A maximum

Current for circuits combined

60 A maximum

60 A maximum

100 A maximum

Convenience outlet type

NEMA 5-15 female
120 V 15 A

NEMA 5-15 female
120 V 15 A

NEMA 5-15 female
120 V 15 A

Protection
APC recommends that a

licensed electrician replace

blown fuses.

All models use UL-Listed Class CC Branch rated fuses 15 A or 20 A

Recommended 15 A fuses

Ferraz-Shawmut ATMR15
Littelfuse KLKR015
Bussman LP-CC-15

Recommended 20 A fuses

Ferraz-Shawmut ATMR20
Littelfuse KLKR020
Bussman LP-CC-20

Environmental

Operating temperature

-25º C to 40º C
-13º F to 104º F

-25º C to 40º C
-13º F to 104º F

-25º C to 40º C
-13º F to 104º F

Operating humidity

5% to 95%

5% to 95%

5% to 95%

Storage temperature

-40º C to 85º C
-40º F to 185º F

-40º C to 85º C
-40º F to 185º F

-40º C to 85º C
-40º F to 185º F

Operating Elevation,

maximum

3000 m (10,000 ft)

3000 m (10,000 ft)

3000 m (10,000 ft)

Storage elevation, maximum

15000 m (50,000 ft)

15000 m (50,000 ft)

15000 m (50,000 ft)

Physical - install the UTS within one foot of the building circuit breaker panel

Unit dimensions

39.4 x 49.8 x 8.3 cm
15.5 x 19.6 x 3.3 in

39.4 x 49.8 x 8.3 cm
15.5 x 19.6 x 3.3 in

39.4 x 59.4 x 8.3 cm
15.5 x 23.4 x 3.3 in

Unit weight

21.5 lbs

21.5 lbs

27.5 lbs

Packaged dimensions

18.7 x 22.9 x 8.4 in

18.7 x 22.9 x 8.4 in

18.7 x 26.8 x 8.4 in

Packaged weight

25 lbs

25 lbs

31 lbs

Generator Interface - Automatic, Remote Start/Stop

Generator Start/Stop

Individual separate relay contact closure; programmable, normally open (NO) and

normally closed (NC)

Start Delay

30 sec to 60 min

30 sec to 60 min

30 sec to 60 min

Stop Delay

30 sec to 60 min

30 sec to 60 min

30 sec to 60 min

Generator Exercise (Test)

Every two weeks

Every two weeks

Every two weeks

Options & Accessories

Universal Transfer Switch Hardwire Kit
APC UTS Automatic Remote Start/Stop Kit
Spare fuses