Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

18

Backup2 Source Type

The factory default setting is UPS. The backup2 power source inlet, located on the

front of the UTS is labeled UPS Inlet as a UPS is the preferred BACKUP2 power

source.
The system setup has three options for backup power:

• Generator
• UPS (recommended BACKUP2 power source)
• Other

Use the down/up arrow keys to select the preferred backup power source.

NOTE:

It is recommended that a UPS be used as BACKUP2 SOURCE TYPE. A UPS provides continuous

battery backup power during utility brownouts, sags, surges, and power outages.
Without the use of a UPS, fully automatic operation of the UTS cannot be guaranteed.
If a UPS is not selected for the BACKUP2 power source be sure that the UNINTERRUPTIBLE option under

Circuit Setup Option 2 is not selected.

Backup2 (UPS) Power Rating

Once the BACKUP2 SOURCE TYPE has been selected, that source type will

appear in the power rating display message. Use the down/up arrow keys to set the

correct power rating for the backup2 power source connected to the UTS.
There are three levels for rapid rating increment changes. Press and hold the down or

up arrow key to adjust the power rating and to move through the three levels described here. To revert back to level 1

release the down arrow key then press and hold the down arrow key.
Level 1 increases or decreases the rating by 5 Watts.
Level 2 increases or decreases the rating by 10 Watts.
Level 3 increases or decreases the rating by 100 Watts.

Circuit 1 setup

Use the down/up arrow keys to scroll through the list of load types. Select the load

type to be supported by circuit 1.

Circuit 2 setup

Use the down/up arrow keys to scroll through the list of load types. Select the load

type to be supported by circuit 2.
Repeat this process for all of the circuits.

NOTE:

UTS6/UTS6H - provide 120 V circuits only

UTS6BI - together, circuits 5 and 6 form a dedicated 240 V circuit. DO NOT use these circuits as individual

120 V circuits.
UTS10BI - Together, circuits 9 and 10 form a dedicated 240 V circuit. DO NOT use these circuits as individual

120 V circuits.

Once all of the UTS parameters have been set, the Setup Wizard ends indicating

that the UTS is setup and ready to operate.

BACKUP2 SOURCE TYPE?
UPS

UPS POWER RATING?
0-1800 WATTS

CKT1 LOAD TYPE?
LIGHT

CKT1 LOAD TYPE?
LIGHT

CKT2 LOAD TYPE?
LIGHT

EXITING WIZARD
UTS IS SETUP & READY