beautypg.com

Specifications – APC UTS6BI User Manual

Page 4

background image

3

Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

Specifications

UTS Specifications

UTS6/UTS6H

UTS6BI

UTS10BI

Electrical

Input - Utility

Input line

Circuit: 12 AWG
Neutral: 10 AWG

Circuit: 12 AWG
Neutral: 10 AWG

Circuit: 12 AWG
Two Neutral: 10 AWG

Voltage range

84 V to 142 V

84 V to 142 V

84 V to 142 V

Nominal voltage

120 V/240 V

single phase

120 V/240 V

single phase

120 V/240 V

single phase

Rated voltage

120 Vac

120 Vac & 240 Vac

120 Vac & 240 Vac

Allowable frequency

47 Hz to 63 Hz

47 Hz to 63 Hz

47 Hz to 63 Hz

Rated current

20 A per circuit

20 A per circuit

20 A per circuit

Input - Backup1 (Generator)

Input line

UTS6 model:

L14-20 male
UTS6H model:

L5-30 male

L14-20 male

L14-30 male

Nominal voltage

UTS6 model:

120 V/240 V

single phase
UTS6H model:

120 V single phase

120 V/240 V

single phase

120 V/240 V

single phase

Rated voltage

120 Vac

120 Vac & 240 Vac

120 Vac & 240 Vac

Frequency

47 Hz to 63 Hz

47 Hz to 63 Hz

47 Hz to 63 Hz

Rated Current

UTS6 model:
20 A
UTS6H model:
30 A

20 A

30 A
50 A hardwired

Maximum voltage

84 Vrms to 142 Vrms

84 Vrms to 142 Vrms

84 Vrms to 142 Vrms

Input - Backup2 (UPS)

Input line

IEC 320 male

IEC 320 male

IEC 320 male

Nominal voltage

120 V single phase

120 V single phase

120 V single phase

Rated voltage

120 Vac

120 Vac

120 Vac

Frequency

47 Hz to 63 Hz

47 Hz to 63 Hz

47 Hz to 63 Hz

Rated Current

15 A

15 A

15 A

Maximum voltage range

84 Vrms to 142 Vrms

84 Vrms to 142 Vrms

84 Vrms to 142 Vrms

This manual is related to the following products: