Specifications – APC UTS6BI User Manual
Page 4
3
Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI
Specifications
UTS Specifications
UTS6/UTS6H
UTS6BI
UTS10BI
Electrical
Input - Utility
Input line
Circuit: 12 AWG
Neutral: 10 AWG
Circuit: 12 AWG
Neutral: 10 AWG
Circuit: 12 AWG
Two Neutral: 10 AWG
Voltage range
84 V to 142 V
84 V to 142 V
84 V to 142 V
Nominal voltage
120 V/240 V
single phase
120 V/240 V
single phase
120 V/240 V
single phase
Rated voltage
120 Vac
120 Vac & 240 Vac
120 Vac & 240 Vac
Allowable frequency
47 Hz to 63 Hz
47 Hz to 63 Hz
47 Hz to 63 Hz
Rated current
20 A per circuit
20 A per circuit
20 A per circuit
Input - Backup1 (Generator)
Input line
UTS6 model:
L14-20 male
UTS6H model:
L5-30 male
L14-20 male
L14-30 male
Nominal voltage
UTS6 model:
120 V/240 V
single phase
UTS6H model:
120 V single phase
120 V/240 V
single phase
120 V/240 V
single phase
Rated voltage
120 Vac
120 Vac & 240 Vac
120 Vac & 240 Vac
Frequency
47 Hz to 63 Hz
47 Hz to 63 Hz
47 Hz to 63 Hz
Rated Current
UTS6 model:
20 A
UTS6H model:
30 A
20 A
30 A
50 A hardwired
Maximum voltage
84 Vrms to 142 Vrms
84 Vrms to 142 Vrms
84 Vrms to 142 Vrms
Input - Backup2 (UPS)
Input line
IEC 320 male
IEC 320 male
IEC 320 male
Nominal voltage
120 V single phase
120 V single phase
120 V single phase
Rated voltage
120 Vac
120 Vac
120 Vac
Frequency
47 Hz to 63 Hz
47 Hz to 63 Hz
47 Hz to 63 Hz
Rated Current
15 A
15 A
15 A
Maximum voltage range
84 Vrms to 142 Vrms
84 Vrms to 142 Vrms
84 Vrms to 142 Vrms