Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI

Problem and Possible Cause

Solution

Problem: UTS configuration errors are found

Cause: Initial UTS configuration is

found to be incorrect.

• Reset the UTS to the factory defaults and begin the setup process again.
Use the System Setup button to scroll through the system setup options. Stop

at RESET TO FACTORY DEFAULTS. Use the down/up arrow keys to

start the Setup Wizard.

Problem: A circuit is mislabeled while using the Setup Wizard

Cause: An error is made while

configuring the UTS circuits.

• Reset the UTS to the factory defaults and begin the setup process again.

Use the System Setup button to scroll through the system setup options.
Stop at RESET TO FACTORY DEFAULTS. Use the down/up arrow keys
to start the Setup Wizard.

• Change the circuit labels. Refer to Circuit Configuration and Setup in the

Operation Manual for details.

Problem: The circuit switches click on and off as power is supplied intermittently to some loads

Cause: The neutral wire is missing or

configured incorrectly.

Connect the neutral wire correctly.

Problem: There is no power to some loads while operating on utility power, and the overload warning appears on

the LCD

Cause: The current going through the

UTS exceeds the maximum rated

specifications.

Reduce the load.