King Electrical Floor Heating Mat Installation Manual
6
STEP 1: Inspecting and testing the cable and floor sensor.
(continued)
1.6 FLOOR SENSOR TEST:
This test measures the resistance of the
floor sensor to verify the integrity of the
component.
A.
Set the multi-meter to read ohms.
B.
Connect the multi-meter leads to the
floor sensor wires.
C.
The meter should read between 8-25k ohms
depending on the ambient temperature
when taking the test. If test results are not
between 8-25k contact King Electrical for
support.
D.
Record the readings on the cable tag and in
the cable test log.
Typical sensor values:
55F (13C ) ________ 17,000 ohms
65F (18C ) ________ 13,000 ohms
75F (24C ) ________ 10,000 ohms
85F (20C ) _________ 8,000 ohms
CABLE TEST LOG
Floor Sensor Test
Tests must be recorded for warranty
Resistance
( + 10%)
Insulation
Test
Model:
Volts:
Factory QC Test
TEST 1. Before installation
TEST 2. After installation, but before
embedding
TEST 3. After embedding
TEST 4. After floor tile