STEP 1: Inspecting and testing the cable and floor sensor.

(continued)

1.6 FLOOR SENSOR TEST:

This test measures the resistance of the
floor sensor to verify the integrity of the
component.

A.

Set the multi-meter to read ohms.

B.

Connect the multi-meter leads to the

floor sensor wires.

C.

The meter should read between 8-25k ohms
depending on the ambient temperature

when taking the test. If test results are not
between 8-25k contact King Electrical for
support.

D.

Record the readings on the cable tag and in

the cable test log.

Typical sensor values:

55F (13C ) ________ 17,000 ohms

65F (18C ) ________ 13,000 ohms
75F (24C ) ________ 10,000 ohms
85F (20C ) _________ 8,000 ohms

CABLE TEST LOG

Floor Sensor Test

Tests must be recorded for warranty

Resistance

( + 10%)

Insulation

Test

Model:

Volts:

Factory QC Test

TEST 1. Before installation

TEST 2. After installation, but before

embedding

TEST 3. After embedding

TEST 4. After floor tile