i. Current Signal Input

Warning! Read Safety Warning on Page 1
before attempting to use this control.

The Signal Isolator accepts 4 – 20 mA DC input to provide 0 – 9 Volts DC
output. Connect the current signal input common (–) to Terminal “5” and the
positive (+) to Terminal “6”, as shown in Figure 3. Other current signal input
ranges can also be used, as described below. Calibrate the Signal Isolator,
as described below.

Note: Two resistors, for 10 – 50 mA and 1 – 5 mA inputs, are supplied in
the hardware bag included with this kit.
4 – 20 DC Signal Input:

No resistor required. Set Jumper J1 in “CUR” position.

10 – 50 mA DC Signal Input (Use Large Resistor with Color Code
“Brown–Green–Brown”):

Install the 150Ω – 1W resistor across Terminals.

“5” and “6”. Set Jumper J1 in “CUR” position.

1 – 5 mA DC Signal Input (Use Small Resistor with Color Code
“Brown–Black–Red”):

Install the 1kΩ – 1/4W resistor across Terminals “5” and “6”. Set Jumper J1

in “VOLT” position.

Procedure to Calibrate the Signal Isolator When Using Current Signal Input:

1. Connect a DC voltmeter (a digital voltmeter is suggested) to Terminals “9” (–) and “10” (+).
2. Apply the minimum signal input current to Terminals “5” (–) and “6” (+).
3. Adjust the MIN Trimpot on the Signal Isolator to obtain an output voltage of 0 Volts DC.
4. Apply the maximum signal input current to Terminals “5” (–) and “6” (+).
5. Adjust the MAX Trimpot on the Signal Isolator to obtain an output voltage of 9 Volts DC.

Notes: 1. To achieve better accuracy, repeat steps 2 – 5. 2. If other than 0 Volts DC (minimum) and 9

Volts DC (maximum) is desired, use the MIN and MAX Trimpots on the Signal Isolator to adjust the
output to the desired voltages in steps 3 and 5.

6

!

5

6

+

Resistor*

(Supplied)

Current Signal Input

150Ω for 10-50 mA

1kΩ for 1-5 mA

FIGURE 3

CURRENT SIGNAL

INPUT CONNECTION

*No resistor required for

4-20 mA.