F. optional equipment – HTP CG300N65 User Manual
Page 6
6
LP-436 REV. 3.21.14
CLASSIFICATION
MG/L OR PPM
GRAINS/GAL
Soft
0
– 17.1
0 - 1
Slightly Hard
17.1
– 60
1
– 3.5
Moderately Hard
60
– 120
3.5
– 7.0
Hard
120
– 180
7.0
– 10.5
Very Hard
180 and over
10.5 and over
If the hardness of the water exceeds the maximum level of 7 grains per gallon, water should be softened to a hardness level no lower
than 5 grains per gallon. Water softened as low as 0 to 1 grain per gallon may be under-saturated with respect to calcium carbonate,
resulting in water that is aggressive and corrosive.
pH of Water
pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water pH. The pH scale ranges from 0 to
14. Water with a pH of 7.0 is considered neutral. Water with a pH lower than 7 is considered acidic. Water pH higher than 7 is
considered alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion damage and heater failures
resulting from water pH levels of lower than 6 or higher than 8 ARE NOT covered by the warranty. The ideal pH range for water
used in a storage tank or a water heater system is 7.2 to 7.8.
Total Dissolved Solids
Total Dissolved Solids (TDS) is a measurement of all minerals and solids dissolved in a water sample. The concentration of total
dissolved solids is usually expressed in parts per million (ppm).
Water with a high TDS concentration will greatly accelerate lime and scale formation in the hot water system. Most high TDS
concentrations precipitate out of the water when heated. This can generate a scale accumulation on the heat transfer surface that will
greatly reduce the service life of a water heater. This scale accumulation can also impede the ability of the heat exchanger to transfer
heat into the water. A heat exchanger damaged or blocked by lime/scale accumulation must be replaced.
The manufacturer of the water heater has no control of water quality, especially TDS levels in your system. Total dissolved solids in
excess of 2,000 ppm will accelerate lime and scale formation in the heat exchanger. Heat exchanger failure due to total dissolved solids
in excess of 2,000 ppm is a non-warrantable condition. Failure of a water heater due to lime scale build up on the heating surface
IS NOT covered by the warranty.
Hardness: 7 grains
Chloride levels: 100 ppm
pH levels: 6-8
TDS: 2000 ppm
Sodium: 20 mGL
F. OPTIONAL EQUIPMENT
Below is a list of optional equipment available from HTP. These additional options may be purchased through your HTP distributor.
High Altitude Kit
Part # 8800P-024
– 125 kBTU
Part # 8800P-025
– 150 kBTU
Part # 8800P-026
– 199.9 kBTU
Part # 8800P-027
– 250 kBTU
Part # 8800P-028
– 300 kBTU
Power Venter
Part # 6060-200
– 125 kBTU
Part # 6060-201
– 150 – 300 kBTU models
Vent Termination Kit
Part # 6060-202
– 125 kBTU
Part # 6060-203
– 150 – 300 kBTU models