The table below lists temperature to hexadecimal conversions.

Setpoint

Hex

Setpoint

Hex

Setpoint

Hex

Setpoint

Hex

68

12

101

2A

134

42

167

5A

69

13

102

2B

135

43

168

5B

70

14

103

2C

136

44

169

5C

71

14

104

2C

137

44

170

5D

72

15

105

2D

138

45

171

5D

73

16

106

2E

139

46

172

5E

74

17

107

2F

140

47

173

5F

Setpoint

Hex

Setpoint

Hex

Setpoint

Hex

Setpoint

Hex

75

17

108

2F

141

47

174

5F

76

18

109

30

142

48

175

60

77

19

110

31

143

49

176

61

78

19

111

32

144

4A

177

62

79

1A

112

32

145

4A

178

62

80

1B

113

33

146

4B

179

63

81

1C

114

34

147

4C

180

64

82

1C

115

34

148

4C

83

1D

116

35

149

4D

84

1E

117

36

150

4E

85

1F

118

37

151

4F

MODBUS Register 40004 Setpoint Conversion Table

86

1F

119

37

152

4F

87

20

120

38

153

50

88

21

121

39

154

51

89

21

122

3A

155

52

90

22

123

3A

156

52

91

23

124

3B

157

53

92

24

125

3C

158

54

93

24

126

3C

159

54

94

25

127

3D

160

55

95

26

128

3E

161

56

96

27

129

3F

162

57

97

27

130

3F

163

57

98

28

131

40

164

58

99

29

132

41

165

59

100

2A

133

42

166

5A


Temperature
The Modbus adapter passes temperature data to the appliance in degrees Fahrenheit. Also, to accommodate decimal places, the
decimal value must be divided by 10. The data sent over the Modbus is passed as an unsigned 16 bit integer. This poses no problem
unless the data becomes negative, such as temperatures below zero. In this case, the compliment has to be calculated as follows:

Temperature to be sent over Modbus = -22

o

F. First multiply by 10. -22 X 10 = -220. Calculate compliment 65536-220 = 65316.


Decimal = 65316. Hex = FF24. Binary = 1111111100100100.

To read the outdoor temperature from the appliance, do the opposite. Read register 40006 and get 65316. Since this value is greater
than 32767, the temperature is negative. To calculate the negative value: 65536

– 65316 = 220, then 220/10 = 22. 22 X -1 = -22

o

F.


For example:

Outdoor temperature from remote sensor on BAS system = 80.5

o

F.

DECIMAL

HEX

805

325

Table 20

Outdoor temperature from remote sensor on BAS system = -25

o

F. Data that needs to be transmitted is -25 X 10 = -250. 65536-

250=65286