beautypg.com

HTP 7350P-629 User Manual

Page 12

background image

12

DISCRETE INPUTS

ADDRESS

DESCRIPTION

DEFAULT

UNIT

MIN

MAX

RESOLUTION

10001

Manual reset high limit 1

0

1 = on, 0 = off

0

1

1

10002

Flow switch 1

0

1 = on, 0 = off

0

1

1

10003

Gas pressure switch 1

0

1 = on, 0 = off

0

1

1

10004

Louver switch 1 (NOT USED)

0

1 = on, 0 = off

0

1

1

10005

Air pressure switch / flap valve

0

1 = on, 0 = off

0

1

1

10006

Blocked drain switch

0

1 = on, 0 = off

0

1

1

10007

Auto reset high limit 1

0

1 = on, 0 = off

0

1

1

10008

Flame 1

0

1 = on, 0 = off

0

1

1

10009

Enable / room thermostat / stage
1

0

1 = on, 0 = off

0

1

1

10010

Tank thermostat

0

1 = on, 0 = off

0

1

1

10011

Extra appliance signal

0

1 = on, 0 = off

0

1

1

10033

Run contacts

0

1 = on, 0 = off

0

1

1

10034

Alarm contact 1
(EXCEPT Versa-Hydro)

0

1 = on, 0 = off

0

1

1

10035

CH pump 1

0

1 = on, 0 = off

0

1

1

10036

DHW pump 1

0

1 = on, 0 = off

0

1

1

10038

Gas valve 1

0

1 = on, 0 = off

0

1

1

10039

System pump

0

1 = on, 0 = off

0

1

1

10049

Appliance 0 burning (same as
10008)

0

1 = on, 0 = off

0

1

1

10050

Appliance 1 burning (same as
10023)

0

1 = on, 0 = off

0

1

1

10051

Appliance 2 burning

0

1 = on, 0 = off

0

1

1

10052

Appliance 3 burning

0

1 = on, 0 = off

0

1

1

10053

Appliance 4 burning

0

1 = on, 0 = off

0

1

1

10054

Appliance 5 burning

0

1 = on, 0 = off

0

1

1

10055

Appliance 6 burning

0

1 = on, 0 = off

0

1

1

10056

Appliance 7 burning

0

1 = on, 0 = off

0

1

1

10057

Appliance 0 lockout (same as
10034)

0

1 = on, 0 = off

0

1

1

10058

Appliance 1 lockout (same as
10042)

0

1 = on, 0 = off

0

1

1

10059

Appliance 2 lockout

0

1 = on, 0 = off

0

1

1

10060

Appliance 3 lockout

0

1 = on, 0 = off

0

1

1

10061

Appliance 4 lockout

0

1 = on, 0 = off

0

1

1

10062

Appliance 5 lockout

0

1 = on, 0 = off

0

1

1

10063

Appliance 6 lockout

0

1 = on, 0 = off

0

1

1

10064

Appliance 7 lockout

0

1 = on, 0 = off

0

1

1

10065

Alarm relay
(Versa-Hydro ONLY)

0

1 = on, 0 = off

0

1

1

INPUT REGISTERS

30001

Discrete inputs 1 - 16

0

NA

0

65535

1

30002

Discrete inputs 17

– 32

0

NA

0

65535

1

30003

Discrete inputs 33

– 48

0

NA

0

65535

1

30004

System / cascade set point /
system pump speed / PUMP 4

0

Deg F

0

212

0, 1

30005

SPEED

0

%

0

100

1

30006

Cascade total power

0

%

0

800

1

30007

Cascade current power

0

%

0

800

1

30008

Outlet set point 0

0

Deg F

-76

212

0, 1

30009

Outlet temp 0

0

Deg F

-76

266

0, 1

30010

Inlet temp 0

0

Deg F

-76

266

0, 1

30011

Flue temp 0

0

Deg F

0

266

0, 1

30012

Firing rate 0 / Appliance 0 pump
speed / Pump 5

0

%

0

100

0, 1

30013

SPEED

0

%

0

100

1

30014

Appliance 0 status code

0

NA

0

65535

30015

Appliance 0 blocking code

0

NA

0

65535

30016

Appliance 0 lockout code

0

NA

0

65535

30017

Outlet set point 1

0

Deg F

-76

212

0, 1