DISCRETE INPUTS
ADDRESS
DESCRIPTION
DEFAULT
UNIT
MIN
MAX
RESOLUTION
10001
Manual reset high limit 1
0
1 = on, 0 = off
0
1
1
10002
Flow switch 1
0
1 = on, 0 = off
0
1
1
10003
Gas pressure switch 1
0
1 = on, 0 = off
0
1
1
10004
Louver switch 1 (NOT USED)
0
1 = on, 0 = off
0
1
1
10005
Air pressure switch / flap valve
0
1 = on, 0 = off
0
1
1
10006
Blocked drain switch
0
1 = on, 0 = off
0
1
1
10007
Auto reset high limit 1
0
1 = on, 0 = off
0
1
1
10008
Flame 1
0
1 = on, 0 = off
0
1
1
10009
Enable / room thermostat / stage
1
0
1 = on, 0 = off
0
1
1
10010
Tank thermostat
0
1 = on, 0 = off
0
1
1
10011
Extra appliance signal
0
1 = on, 0 = off
0
1
1
10033
Run contacts
0
1 = on, 0 = off
0
1
1
10034
Alarm contact 1
(EXCEPT Versa-Hydro)
0
1 = on, 0 = off
0
1
1
10035
CH pump 1
0
1 = on, 0 = off
0
1
1
10036
DHW pump 1
0
1 = on, 0 = off
0
1
1
10038
Gas valve 1
0
1 = on, 0 = off
0
1
1
10039
System pump
0
1 = on, 0 = off
0
1
1
10049
Appliance 0 burning (same as
10008)
0
1 = on, 0 = off
0
1
1
10050
Appliance 1 burning (same as
10023)
0
1 = on, 0 = off
0
1
1
10051
Appliance 2 burning
0
1 = on, 0 = off
0
1
1
10052
Appliance 3 burning
0
1 = on, 0 = off
0
1
1
10053
Appliance 4 burning
0
1 = on, 0 = off
0
1
1
10054
Appliance 5 burning
0
1 = on, 0 = off
0
1
1
10055
Appliance 6 burning
0
1 = on, 0 = off
0
1
1
10056
Appliance 7 burning
0
1 = on, 0 = off
0
1
1
10057
Appliance 0 lockout (same as
10034)
0
1 = on, 0 = off
0
1
1
10058
Appliance 1 lockout (same as
10042)
0
1 = on, 0 = off
0
1
1
10059
Appliance 2 lockout
0
1 = on, 0 = off
0
1
1
10060
Appliance 3 lockout
0
1 = on, 0 = off
0
1
1
10061
Appliance 4 lockout
0
1 = on, 0 = off
0
1
1
10062
Appliance 5 lockout
0
1 = on, 0 = off
0
1
1
10063
Appliance 6 lockout
0
1 = on, 0 = off
0
1
1
10064
Appliance 7 lockout
0
1 = on, 0 = off
0
1
1
10065
Alarm relay
(Versa-Hydro ONLY)
0
1 = on, 0 = off
0
1
1
INPUT REGISTERS
30001
Discrete inputs 1 - 16
0
NA
0
65535
1
30002
Discrete inputs 17
– 32
0
NA
0
65535
1
30003
Discrete inputs 33
– 48
0
NA
0
65535
1
30004
System / cascade set point /
system pump speed / PUMP 4
0
Deg F
0
212
0, 1
30005
SPEED
0
%
0
100
1
30006
Cascade total power
0
%
0
800
1
30007
Cascade current power
0
%
0
800
1
30008
Outlet set point 0
0
Deg F
-76
212
0, 1
30009
Outlet temp 0
0
Deg F
-76
266
0, 1
30010
Inlet temp 0
0
Deg F
-76
266
0, 1
30011
Flue temp 0
0
Deg F
0
266
0, 1
30012
Firing rate 0 / Appliance 0 pump
speed / Pump 5
0
%
0
100
0, 1
30013
SPEED
0
%
0
100
1
30014
Appliance 0 status code
0
NA
0
65535
30015
Appliance 0 blocking code
0
NA
0
65535
30016
Appliance 0 lockout code
0
NA
0
65535
30017
Outlet set point 1
0
Deg F
-76
212
0, 1