beautypg.com

F. rate and temperature conversions – HTP 7350P-629 User Manual

Page 17

background image

17


Please note that with Modbus communication connected only to the master appliance, only total cascade information can be seen
through the communications link. Information from the follower boilers is limited to follower appliance rate command, supply
temperature, fault code, and fault status.

If you want to see complete data from each follower, or use the Modbus master to control cascading of multiple appliances, each
appliance will need a Modbus communication board.

Monitoring Only
Any appliance can be equipped with the Modbus communication accessory and then be set up to operate with its own internal controls.
The Modbus master can then poll the Modbus accessory for the read only variables.

F. RATE AND TEMPERATURE CONVERSIONS

Rate
When issuing a rate command, the rate can be communicated as percent modulation or a desired set point temperature depending on
the setting of parameter 16 in the appliance Installer Menu. Proper data format for the modulation percentage is direct conversion to
hexadecimal. This conversion can be accomplished through online number based converters or some scientific calculators.

For example:

RATE %

HEX

0

00

20

14

45

2D

60

3C

80

50

95

5F

100

64

Table 18

Temperature Conversions
To send a desired set point, the hexadecimal value must be determined through linear interpolation of programmable parameters on
the BMS setup menu.

BMS temperature set point at low analog input

BMS temperature set point at high analog input


These variables set the temperature values corresponding to the minimum and maximum voltage settings of the 0

– 10 volt signal. The

defaults are as follows:

PARAMETER

DEFAULT VALUES

DEFAULT

Deg C

Deg F

Voltages

BMS temperature set point at low analog input

21

69.8

2

BMS temperature set point at high analog input

82

179.6

10

Table 19

For example: Send a set point of 110

o

F. The formula to use for the interpolation is:


Rate Command =

(Desired set point

– BMS temp at low analog input) (High voltage – low voltage) + Low voltage

(BMS temp at high analog input

– BMS temp at low analog input)


From the default values:
Desired set point = 110
BMS temp at low analog input = 68
BMS temp at high analog input = 158
High voltage = 10
Low voltage = 2

[(110 - 69.8)(10-2)/(179.6 - 69.8)] + 2 = 4.92 volts

(4.92/10) x 100 = 49.2

49 = 31 Hexadecimal

A value of [00] [31] in hexadecimal would be written to holding register 40003 to issue a command for a 110

o

F set point.