Ronan id fs), Ronan id fsm), 0 sequences (cont.) – Ronan X11SN User Manual
Page 13
PROCESS
PROCESS
PROCESS
PROCESS
NORMAL
ABNORMAL OR
NORMAL
ABNORMAL OR
NORMAL
ABNORMAL OR
NORMAL
SUBSEQUENT TO
ABNORMAL
ACKNOWLEDGE
WHILE NORMAL
SUBSEQUENT
ALARM
ACKNOWLEDGE WHILE ABNORMAL
NORMAL
ACKNOWLEDGED
FIRST ALARM
ACKNOWLEDGE
(FIRST OUT RESET)
FIRST TO
ABNORMAL
RETURN TO
NORMAL
ON
OFF
ON
SLOW FLASHING
SEQUENCE
SEQUENCE
SEQUENCE
SEQUENCE
VISUAL
VISUAL
VISUAL
VISUAL
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
SILENT
SILENT
AUDIBLE
SEQUENCE DIAGRAM
9.5 F2A, Automatic Reset First Out
with No Subsequent Alarm
Flashing
(Ronan ID FS)
1. Acknowledge, reset, and test push
buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until
acknowledged.
4. Flashing indication for first alarm only.
New subsequent alarms have the
same visual indication as acknow-
ledged alarms.
5. First out indication is reset when
acknowledged.
6. Automatic reset of acknowledged
alarm indications when process
conditions return to normal.
7. Operational test.
9.6 F2M, Manual Reset First Out with
No Subsequent Alarm Flashing
(Ronan ID FSM)
1. Acknowledge, reset, and test push
buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until
acknowledged.
4. Flashing indication for first alarm only.
New subsequent alarms have the
same visual indication as acknow-
ledged alarms.
5. First out indication is reset when
acknowledged.
6. Manual reset of acknowledged alarm
indications after process conditions
return to normal.
7. Operational test.
12
9.0 SEQUENCES (CONT.)
PROCESS
PROCESS
PROCESS
PROCESS
NORMAL
ABNORMAL OR
NORMAL
ABNORMAL OR
NORMAL
ABNORMAL OR
NORMAL
SUBSEQUENT TO
ABNORMAL
SUBSEQUENT
ALARM
ACKNOWLEDGE
NORMAL
ACKNOWLEDGED
FIRST ALARM
ACKNOWLEDGE
(FIRST OUT RESET)
FIRST TO
ABNORMAL
RESET WHILE
NORMAL
ON
OFF
ON
SLOW FLASHING
SEQUENCE
SEQUENCE
SEQUENCE
SEQUENCE
VISUAL
VISUAL
VISUAL
VISUAL
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
SILENT
SILENT
AUDIBLE
SEQUENCE DIAGRAM