Maintenance, Replacing the filter-drier, Change filter – Robinair 34134Z Refrigerant Recovery, Recycle, Recharge Unit User Manual
Page 29
Recover/Recycle/Recharge Unit
27
Maintenance
The filter-drier inside the unit removes acid, particulates, and moisture from
refrigerant during the recovery function. To provide adequate contaminant
and moisture removal, the filter-drier must be replaced after every 150 lbs.
(68 kg) of refrigerant recovered. The following will appear in the display:
Use the following steps to replace the filter-drier.
NOTE: For maximum unit performance, use only No. 34430 SPX/ROBINAIR
filter-drier. To avoid service delays, keep extra filter-driers on hand. Refer to
the Replacement Parts
section of this manual.
1. Plug the power cord into a correct voltage outlet, and turn the unit on.
2. Verify the service hoses are NOT connected to a vehicle.
Replacing the Filter-drier
CHANGE FILTER
Control Panel
3. On the control panel, open both panel valves.
4. Press the Mode key until RECOVER XX.XX displays on the screen.
5. Press the Start/Stop key.
6. Watch the low-side gauge. When the gauge pressure reaches 10 in. Hg
(34 kPa) vacuum, close both panel valves.
7. Turn the unit’s power switch off.
8. Remove the unit’s power cord from the outlet.