Recover/Recycle/Recharge Unit

11

7. Press the Start/Stop key. The internal storage vessel begins filling, and the

screen displays the amount of refrigerant being transferred to the internal
storage vessel.

8. The unit will automatically stop when 15 lbs. (7 kg) has been transferred to

the internal storage vessel. The display will flash between:

and

NOTE: Do not drain oil until the following steps are complete. Drain oil
instructions are at the bottom of this page.

9. Unstrap the source tank, remove it from its compartment, then close the

source tank valve.

10. Disconnect the hose from the tank.

11. Cap the source tank with its original tank cap. For storage, place the source

tank upright in the source tank compartment. Secure the source tank in
place by wrapping the strap around the tank, and then fastening the strap.

12. Do the following to clear the service hoses:

a. Press Mode key to:

b. Press Start/Stop key to start hose clearing.

c. Watch the low-side gauge. When the gauge pressure reaches 10 in. Hg

(34 kPa) vacuum, press Start/Stop key to stop the clearing process.

13. Close the low-side panel valve.

Drain Oil

1. On the control panel, open the oil-drain valve. Watch the oil drain into the

oil-drain bottle. It may take 30 seconds or more for the oil to start draining.

2. When oil stops draining, close the oil-drain valve.

RECOVER

XX.XXKG

Adding Refrigerant to the Internal Storage Vessel

contd.

Initial Setup

DRAIN OIL

RECOVER

XX.XXLBS