Initial setup, Contd – Robinair 34134Z Refrigerant Recovery, Recycle, Recharge Unit User Manual
Page 13
Recover/Recycle/Recharge Unit
11
7. Press the Start/Stop key. The internal storage vessel begins filling, and the
screen displays the amount of refrigerant being transferred to the internal
storage vessel.
8. The unit will automatically stop when 15 lbs. (7 kg) has been transferred to
the internal storage vessel. The display will flash between:
and
NOTE: Do not drain oil until the following steps are complete. Drain oil
instructions are at the bottom of this page.
9. Unstrap the source tank, remove it from its compartment, then close the
source tank valve.
10. Disconnect the hose from the tank.
11. Cap the source tank with its original tank cap. For storage, place the source
tank upright in the source tank compartment. Secure the source tank in
place by wrapping the strap around the tank, and then fastening the strap.
12. Do the following to clear the service hoses:
a. Press Mode key to:
b. Press Start/Stop key to start hose clearing.
c. Watch the low-side gauge. When the gauge pressure reaches 10 in. Hg
(34 kPa) vacuum, press Start/Stop key to stop the clearing process.
13. Close the low-side panel valve.
Drain Oil
1. On the control panel, open the oil-drain valve. Watch the oil drain into the
oil-drain bottle. It may take 30 seconds or more for the oil to start draining.
2. When oil stops draining, close the oil-drain valve.
RECOVER
XX.XXKG
Adding Refrigerant to the Internal Storage Vessel
contd.
Initial Setup
DRAIN OIL
RECOVER
XX.XXLBS