Initial setup, Contd, Adding refrigerant to the internal storage vessel – Robinair 34134Z Refrigerant Recovery, Recycle, Recharge Unit User Manual

Page 12

background image

©

2003 SPX Corporation

10

1. Connect the low-side tank adapter (from the accessory kit) to the liquid

valve on the refrigerant source tank.

NOTE: If using a refillable source tank,

connect the tank adapter to the vapor valve.

R-134a Tank Adapter

2. Connect the service coupler of the low-side hose (blue) to the refrigerant

source tank.

3. Open the valve on the source tank, and place the tank upside down in the

source tank compartment. Secure the source tank in place by wrapping the
strap around the tank, and then fastening the strap.

4. The screen should display RECOVER XX.XXLBS. If it does not, scroll

through the functions by pressing the Mode key until RECOVER XX.XXLBS
is displayed.

5. Press the Arrow keys to adjust the recover weight to 15 lbs. (7 kg).

6. On the control panel, open the low-side valve; verify the high-side valve is

closed.

Initial Setup

Adding Refrigerant to the Internal Storage Vessel

contd.