Model 178002K/178012K Recovery/Recycling/Recharging Unit

35

OIL/drn

(Flashes alternately) Drain; open the oil drain valve to relieve the pressure
in the unit.

FIL

Filter/drier change procedure is being performed.

FULL

The tank is full; recovery stops automatically.

HI-P

High pressure; the unit pressure is greater than 435 psi.

OIL

Change vacuum pump oil; it has been 10 hours since the last oil change.

R12

R-12; indicates R-12 or other refrigerant type requiring

1

/

4

” flare

fittings.

SCAL

Scale problem; the scale is broken or disconnected, or the tank has
exceeded 80 pounds gross weight.

U-HI

High pressure to vacuum pump; prevents blowing refrigerant through the
vacuum pump. To relieve pressure, perform a recovery process (see the
Operating Instructions).

99LB

The maximum amount displayed during recovery is 99 pounds. Press
SHIFT/RESET to clear the display.