Operating instructions, Recovery procedures warning – Robinair 178012K Recovery, Recycling, Recharging Unit User Manual
Page 12
© 2000 Robinair, SPX Corporation
10
Operating Instructions
Diagram of Control Panel
Low Side
Gauge
High Side
Gauge
High
Side
Valve
Liquid/Vapor
Indicator
Display
Main
Power
Switch
Air
Purge
Valve
Keypad
Low
Side
Valve
Air Purge Gauge
RECOVERY PROCEDURES
WARNING!
Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Disconnect hoses with extreme
caution!
All hoses may contain refrigerant under pressure. Read and follow all
warnings at the beginning of this manual before operating the unit.
Before beginning recovery, be sure your unit is set up as described in the Set-Up
Instructions. Also be sure there is vacuum pump oil in the vacuum pump.
1. Connect the high and low side hoses to the A/C-R system, as you would normally
connect your manifold gauge set.
2. Be sure both the high and low side valves on the control panel are open. Also be
sure both valves on the tank are open.
3. Plug the unit into the proper voltage outlet, and turn on the MAIN POWER
switch. The display shows either “134a” (which indicates R-134a automotive
refrigerant that uses
1
/
2
” Acme fittings) or “R12” (which indicates all other refriger-
ant types that use
1
/
4
” flare fittings).
4. Press SHIFT/RESET, then press RECOVER.