CONTROL CONDITIONS

Power Up

On power up, the system does several checks to

determine hardware status. It checks various sig-

nals to determine that there are no faults, including

feedback from the Variable Voltage Output and

High Voltage Inputs to determine system status.

If it determines that it is OK to start, the Check

display on the run menu changes from NoGo to

OK and System Status changes to OK.

HV On

When the HV On signal is received, the system

status changes to "Starting" and the Variable Volt-

age Output is increased until the Indpendent Value

rises to within a tolerance window (currently +/-3)

of the setpoint value. Then the System Status

changes to "Running".

Setpoint Changed

If the setpoint changes outside the control window,

the status changes to "Rising" or "Falling" until the

Independent Value again reaches the window at

which point it returns to "Running".

HV Off

On HV Off the system immediately sets the Vari-

able Voltage Output to zero volts, disables the

HV Relay and goes to Stop Mode. The System

Check goes to NoGo until the High Voltage and

Variable Voltage Output feedback again reach the

pre-determined value.

SYSTEM STATUS (STS)

OK

System is off and ready to start.

Starting/Rising/Falling

System is changing from one voltage/current value

to another. Di/dt and dv/dt checks are disabled.

Running

System is attempting to keep a steady value on

Setpoint (the Independent Value). All enabled

checks are active.

Stopping

System is off and waiting to transient voltages/

currents to stop.

Warning

System has detected a current or voltage condi-

tion within 10% of the limit settings.

Fault

System has detected a fault condition, stopped

and will not allow starting until the fault is cleared.

If the fault condition has not been cleared, it may

immediately fault without starting.

SYSTEM CHECK (CHK)

OK

System has passed the checks and is ready to start.

NoGo

System has detected excessive voltage on the

High Voltage or Variable Voltage Output Feedbacks

and will not allow a start.

High Voltage Controller - Operation