Electrical specifications – FIREPOWER MXL-IQ User Manual
Page 8
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety
equipment will be considered a misapplication of Fire Safety equipment and as
such void all warranties either expressed or implied with regard to loss, damage,
liabilities and/or service problems.
Electrical Specifications
SMB-2 Analog Device Loops (TB2 and TB3)
1.
Electrical Ratings:
Supervisory
30 VDC max, 66mA max.
Alarm
30 VDC max, 66mA max.
(60 devices in alarm)
2. All wiring must be in accordance with Article 760 of
NEC or local building codes.
3. Only the following list of devices may be used.
A maximum of 60 devices in any combination may
be connected to a single analog loop. The UL
identifiers for compatibility are the same as the
model names specified in Table 1.
4. No end of line device is required.
5. Both circuits are power limited to NFPA 70/NEC
760. Each detector, or group of detectors, requires a
two wire circuit of minimum 18 AWG thermoplastic
fixture wire.
6. Total circuit resistance must not exceed 100 ohms.
Maximum capacitance:
0.4uF, between loop+
and loop-
0.8uF, between loop+
and chassis
0.8uF, between loop-
and chassis
7. T-tapping is not allowed on Style 6 loops.
8. See P/N 315-092772 for more information on wiring.
SMB-2 AUX Power (TB5, 9-12)
1. AUX power is available on TB5 terminals 9-12.
2. All wiring must be in accordance with Article 760 of
NEC or local building codes.
3. Aux power is power limited to NFPA 70/NEC 760.
4.
Electrical Ratings:18-31 VDC, 1A max.
5. See P/N 315-092772 for more information on wiring.
SMB-2 Notification Appliance Circuits (TB-5, 1-4 and
TB5, 5-8)
1. These notification appliance circuits are for alarm
notification appliances only (NFPA 72). For Municipal
Tie (NFPA 72, Chapter 4), Releasing (NFPA 13) or
Leased Line (NFPA 72, Chapter 4), use model
CSM-4
2. All wiring must be in accordance with Article 760 of
NEC or local building codes.
3. Both notification appliance circuits are power
limited to NFPA 70/NEC 760.
4.
Electrical Ratings:
Supervisory
18-31 VDC, 12mA max.
Alarm
18-31 VDC, 1.5A max
5.
End of Line Device: Use Siemens Fire Safety
EOL 2.2K, 1/2W,
P/N 140-820380
6.
Line Resistance:
Not to exceed 3 ohms
total.
7. See P/N 315-092772 for more information on wiring.
TABLE 1
COMPATIBLE DEVICES
* The FP-11/FPT-11 is only compatible with MXL-IQ Rev. 6.0 or greater firmware.
** The ILP-2 is only compatible with MXL-IQ Rev. 3.0 or greater firmware.
† When the CSG-M is configured, the DUCT application must be selected
when the device is used in an air duct housing or in a spot duct application.
January 2006
Supersedes sheet dated 6/03
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis
1/06
5M
SFS-IG
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
Canada L6T 5E4
Tel: (905) 799-9937
FAX: (905) 799-9858