CCU/M and RDM-MXL
CCU/M Alphanumeric Pager Interface
The CCU/M is a ancillary module that connects to the
PIM-1 to transmit MXL-IQ status information in text
message format to an alphanumeric pocket pager. The
CCU/M can be connected to an existing phone line and
can dial out to a pager using its onboard modem to
transmit information via a paging service. The CCU/M
can also connect directly to an existing on-site paging
system. Through programming the CCU/M can send
different types of events to different pagers. Up to 8
different messages can be sent to pagers directly from
the CCU/M. Alarms, Troubles, Supervisory, Security,
Arm/Disarm, Status Points, Audible Status, and Reset
can be directed to all or only certain alphanumeric
pocket pagers.
MSE-3L MXL-IQ Enclosure/Door
The MSE-3L is a sheetmetal backbox for the MXL-IQ
system. The MSE-3L supports mounting for the SMB-2,
MPS-6, MPS-12, MPS-12-220, MPS-12-240, MKB-4 and
either one MOM-2 or one MOM-4 cardcage. The MSE-3L
dimensions are 27
1
/
16
”H x 21
1
/
8
”W x 6”D. The IQ-DFL
plate (500-695436) is also available for use with the
MSE-3L to provide full deadfront construction. The MET-
3L (500-695437) flush trim mounting kit is also available
for use with the MSE-3L enclosure. The MET-3L pro-
vides an optional 1” trim mounting ring around the
MSE-3L. The MSE-3L enclosure also has provision for
mounting a PSR-1 remote power supply, for use in place
of the SMB-2 for MXL and MXLV applications. When the
PSR-1 is mounted in the MSE-3L enclosure the IQ-
BLANK (500-695438) blank plate is available to cover the
cutout in the MSE-3L door. Other versions of the MSE-
3L include; MSE-3LR - Red version of the MSE-3L and the
MET-3LR - Red version of the MET-3L trim ring kit.
MSE-3L
14 in
The RDM-MXL in combination with the RDM-PC pro-
vides the ability to call up an MXL, MXL-IQ or MXLV
system to check on the system status. The RDM-PC
connects a remote computer to the MXL equipped wit
the RDM-MXL. The RDM-PC initiates a call to the MXL’s
RDM-MXL module. The RDM-MXL answers the call.
The RDM-PC identifies itself with the login name. As a
built-in security measure, when the login name is
recognized by the RDM-MXL, it then hangs up and
initiates a call back to verify the login and password.
Once the login and password is verified, the operator is
on-line with the MXL. The operator can list system
status, alarms, troubles, supervisories, and/or security
events!
REP-1
The REP-1 is an optional MXL module that extends
the distance of the MXL’s RS-485 network. The REP-1
provides the ability to support various wiring configu-
rations, including series and star configurations. The
REP-1 provides the ability to support NFPA Style 4
or Style 7 network communications wiring. The REP-1
can be used to provided network wiring between
MXL panels or MXLR panels. The REP-1 is a one -half
slot card that plugs into a MOM-4 or MOM-2
cardcage. The REP-1 allows MXL network distances
to be expanded to allow greater application flexibility.
The REP-1 is an RS-485 repeater module capable of
being configured as one Style 7 or two Style 4 net-
work communication lines.
RDM-MXL, RDM-PC
REP-1