Troubleshooting – Fire Fighting Enterprises FIRERAY 3000 User Manual
Page 14

14
E-00 AIM not recognised
Refer to manufacturer for further technical
assistance
E-01
Receiver Communications Fault
Check wiring between Controller and
Receiver
E-02
‘Find’ not successfully executed
Follow ‘Find’ process
E-03
Compensation limit reached
Clean and re-align system
E-04
Receiver missed too many readings, or lost
sync with the Transmitter
Ensure clear line of sight from Transmitter to
Receiver
E-05
Receiver is not aligned
Follow alignment procedure
E-06
Rapid Obscuration Fault
Ensure clear line of sight from Transmitter to
Receiver
E-07
Signal High Fault
Ensure there is no stray light from another source
E-15
Signal too low at end of alignment
Ensure clear line of sight from Transmitter to
Receiver. Ensure alignment of Transmitter AND
Receiver. Do not exit whilst alignment status LEDs
are still flashing
E-16
Signal too high at end of alignment
Follow alignment procedure again. Do not exit
whilst alignment status LEDs are still flashing
E-18
Short circuit detected on communications
between Controller and Receiver
Check wiring between Controller and Receiver
E-19
IR signal integrity fault
Check there are no strong sources of light near the
Receiver, or direct sunlight
E-20 Ambient light fault
Check there are no strong sources of light near the
Receiver, or direct sunlight
E-21
Power too low fault
Check power supply to Controller
17. Troubleshooting