beautypg.com

Troubleshooting – Fire Fighting Enterprises FIRERAY 3000 User Manual

Page 14

background image

14

E-00 AIM not recognised

Refer to manufacturer for further technical

assistance

E-01

Receiver Communications Fault

Check wiring between Controller and

Receiver

E-02

‘Find’ not successfully executed

Follow ‘Find’ process

E-03

Compensation limit reached

Clean and re-align system

E-04

Receiver missed too many readings, or lost

sync with the Transmitter

Ensure clear line of sight from Transmitter to

Receiver

E-05

Receiver is not aligned

Follow alignment procedure

E-06

Rapid Obscuration Fault

Ensure clear line of sight from Transmitter to

Receiver

E-07

Signal High Fault

Ensure there is no stray light from another source

E-15

Signal too low at end of alignment

Ensure clear line of sight from Transmitter to

Receiver. Ensure alignment of Transmitter AND

Receiver. Do not exit whilst alignment status LEDs

are still flashing

E-16

Signal too high at end of alignment

Follow alignment procedure again. Do not exit

whilst alignment status LEDs are still flashing

E-18

Short circuit detected on communications

between Controller and Receiver

Check wiring between Controller and Receiver

E-19

IR signal integrity fault

Check there are no strong sources of light near the

Receiver, or direct sunlight

E-20 Ambient light fault

Check there are no strong sources of light near the

Receiver, or direct sunlight

E-21

Power too low fault

Check power supply to Controller

17. Troubleshooting