Appendix A - DIP Switch Settings
The 10-position DIP Switch is used to configure:
• RS-485 Communication protocol (pos 1)
• Ethernet Communication protocol (pos 2)
• RS-485 Baud rate (pos 3 & 4)
• Single channel input mode for RJ45 style connector and ST (screw terminal); dual-
channel only available on RJ45. (pos 5)
• Spare Pos 7 & 8
• RS-485 Bias (pos 9 & 10); only one device on the network needs to have biasing.
The communication baud rate is selected by means of a DIP Switch on the circuit
board. There are four (4) selections: 9600 (factory default), 19.2k, 38.4k, and 76.8k
bps; higher baud rate would reduce cabling length. When connecting the device to an
RS-485 network needing the use of biasing the RS-485 line, turn on DIP Switch pos 9
and pos 10. After changing the DIP switch selections (1.8), restart the device for the
new settings to take effect (9&10 for BIAS doesn’t require CPU restart).
Fig. 8. DIP Switch Baud Rates.
M33277A
3
4
BAUD RATE
ON
ON
9600
OFF ON
19200
ON OFF
38400
OFF OFF
76800