E-Mon E20-6003200J-G-KIT User Manual
Page 37

GREEN CLASS METER
37
62-0415-01
Input Voltage
Configuration
3-wire (Delta) Or 4-wire (Wye)
Mains Voltage Input Up To 480 VAC RMS Available
Input Power
6 VA Maximum Rating
Current Sensor
Rating
Up To 3200 Amps RMS AC Available
Power Factor
0.5 Leading Or Lagging
Line Frequency
50-60 Hz
Metering Accuracy
Certified To ANSI C12.16 (+/-% From 1- 100% Of Rated Load)
Voltage Operating
Range
+/-10% Of Rated Load
Temperature Range -20 C To +50 C (Standard indoor enclosure):
Temperature Range -20 C To +70 CNEMA 4X (NEMA 4X outdoor enclosure)
Relative Humidity
Range
0-95% Non-condensing
Altitude
2000 Meters Maximum
Voltage Overload
+25% Continuously: +100% For 20 Cycles
Current Sensor
Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree
Degree 2 In Accordance With IEC 664
Installation
(Overvoltage)
Category
Category 111
Measurement
Category
Category 111
Enclosure Material
Indoor Housing Rating (Standard): NEMA 12
Outdoor Housing Rating (Optional): NEMA 4X
Display Readout
KWh Accumulated
Standard Ranges
4-Wire Wye, 120/208 VAC: 100, 200, 400, 800,1600,3200 Amp
2 Phase, 120/240 VAC: 100, 200, 400, 800,1600,3200 Amp
4-Wire Wye, 277/480 VAC: 100, 200, 400, 800,1600,3200 Amp
3-Wire Delta, 220/240 VAC: 100, 200,400,800,1600,3200 Amp
3-Wire Delta, 480 VAC: 100, 200, 400, 800,1600,3200 Amp
- E20-6001600J-G-KIT E20-600800-J-G-KIT E20-600400-J-G-KIT E20-600200-J-G-KIT E20-600100-J-G-KIT E20-4803200J-G-KIT E20-4801600J-G-KIT E20-480800-J-G-KIT E20-480400-J-G-KIT E20-480200-J-G-KIT E20-480100-J-G-KIT E20-2083200J-G-KIT E20-2081600J-G-KIT E20-208800-J-G-KIT E20-208400-J-G-KIT E20-208200-J-G-KIT E20-208100-J-G-KIT