3 current sensor installation & wiring – E-Mon E20-6003200J-G-KIT User Manual
Page 10
GREEN CLASS METER
62-0415-01
10
8. Using an AC Voltmeter, verify the input voltage readings are within the limits
specified below.
9. Remove power from the unit by de-energizing the external switch.
NOTE: For 3-Wire systems, the voltages are measured Phase to Phase. On 4-Wire
systems the voltages are measured Phase to Neutral.
4.3 Current Sensor Installation & Wiring
Once the AC voltages have been confirmed to be within acceptable limits, you are
ready to install the current sensors. The MAIN power board contains three header
connectors located at the bottom right of the board. The connectors are labeled A, B,
and C along with conductor color indication. This format must be followed in order for
the meter to function correctly.
The Green Class meter will be used with one of two basic types of current sensors:
a. Split-Core Current Sensor: This sensor opens so that it can be attached
around the circuit conductor being monitored without interrupting power.
Unless otherwise
specified, all Green Class meters are supplied with this sensor type.
b. Solid-Core Current Sensor: This sensor does not open and requires the
monitored conductor be removed from the circuit to install the current sensor.
This type is only supplied when specified at time of order.
NOTE: The unit serial label specifies if the unit is set up for split or solid core current
sensors. See ordering information for details.
Both types of current sensors output a 0-2 VAC signal proportional to the current being
measured.
The current sensors must be matched with the voltage phases. The A phase sensor
must be monitoring the same phase as the A phase voltage. B & C phase sensors
must also monitor the same phase as their respective voltage inputs.
Meter Input Voltage
Configuration
Nominal Voltage
Limits (+/- 10%)
120/208V, 3 Ph, 4 Wire
120 VAC (L-N)
108 to 132 VAC
277/480V, 3 Ph, 4 Wire
277 VAC (L-N)
249 to 305 VAC
240V, 3 Ph, 3 Wire
240 VAC (L-L)
216 to 264 VAC
480V, 3 Ph, 3 Wire
480 VAC (L-L)
432 to 528 VAC
347/600V, 3 Ph, 4 Wire
347 VAC (L-N)
540 to 660 VAC
- E20-6001600J-G-KIT E20-600800-J-G-KIT E20-600400-J-G-KIT E20-600200-J-G-KIT E20-600100-J-G-KIT E20-4803200J-G-KIT E20-4801600J-G-KIT E20-480800-J-G-KIT E20-480400-J-G-KIT E20-480200-J-G-KIT E20-480100-J-G-KIT E20-2083200J-G-KIT E20-2081600J-G-KIT E20-208800-J-G-KIT E20-208400-J-G-KIT E20-208200-J-G-KIT E20-208100-J-G-KIT