4.0 METER INSTALLATION
4.1 Mounting the Meter
STEP 1: Using the appropriate sized mounting hardware, fasten the Class 1000 meter
enclosure to the selected mounting surface. The four mounting holes are centered
6.75” H x 4” W. The mounting hole spacing is identical for either the UL Type 1 or
NEMA 4X enclosure.
NOTE: Only the NEMA 4X enclosed unit is suitable for outdoor environmental condi-
tions. Units housed in UL Type 1 enclosures must only be installed in indoor
environments where it will not be affected by the elements, such as moisture
and extreme temperatures.
4.2 Main Power Board Connections
STEP 1: Install a temporary ground for ESD (Electrostatic Discharge) protection. With
all circuits de-energized, connect a temporary protective earth ground connection for
ESD protection. Prior to performing any unit wiring, be sure to discharge any static on
your person.
STEP 2: Install the Class 1000 Protective Earth Ground. Connect an earth ground wire
to the Class 1000 protective earth ground terminal screw located on the right side of
the line voltage terminal block. After installing the protective earth ground wire,
securely fasten the protective earth ground screw.