13
62-0388-01
4.5 Installing the Solid-Core Current Sensor Assembly
The optional solid-core current sensors can be installed in the same applications as
the standard split-core units, however, the conductors that they are monitoring must
first be disconnected.
NOTE: Under no circumstances is this operation to take place without shutting off the
power to the conductor(s) being monitored.
With the power off, disconnect the conductor from its breaker or terminal. Slide the
solid-core current sensor over the conductor, making sure that the indicator on the
sensor is pointing in the direction of the load. After this is done, reconnect the
conductor and verify that it is properly installed.
Run the black and white wires from the solid-core current sensors and install them
according to the standard installation diagram. When this is completed, the power to
the monitored conductor can be turned back on.
Fig. 5. Solid Core Sensor Assembly