Installation, Warning – Fulton Vertical Coil (FT-C_S) Thermal Fluid (hot oil) Heater User Manual
Page 26

© The Fulton Companies 2013
2-20
INSTALLATION
FTCS-IOM-2013-1114
SECTION 2
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
TABLE 8 - RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 150# GASKETS SAE
GRADE 5 BOLTS OR EQUAL
Nominal Flange Size
(inches)
Number of Bolts
Diameter of Bolts
(inches)
Preferred Torque Req.
Per Bolt (ft-lb)
1/2
4
1/2
30
3/4
4
1/2
30
1
4
1/2
30
1 1/4
4
1/2
30
1 1/2
4
1/2
30
2 4
5/8
60
2 1/2
4
5/8
60
3 4
5/8
60
4
8
5/8
60
5
8
3/4
100
6
8
3/4
100
8
8
3/4
100
10
12
7/8
160
TABLE 9 - RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 300# GASKETS SAE
GRADE 5 BOLTS OR EQUAL
Nominal Flange Size
(inches)
Number of Bolts
Diameter of Bolts
(inches)
Preferred Torque Req.
Per Bolt (ft-lb)
1/2
4
1/2
30
3/4
4
5/8
60
1
4
5/8
60
1 1/4
4
5/8
60
1 1/2
4
3/4
100
2 8
5/8
60
2 1/2
8
3/4
100
3 8
3/4
100
4
8
3/4
100
5
8
3/4
100
6
12
3/4
160
8
12
7/8
245
10
16
1
160