5a. NEMA 5-15R receptacles

Six 15 Amp rated NEMA 5-15R outlets provide a nominal 120 Vac for multiple small loads.

5b. NEMA 5-15R receptacle circuit breaker

Each NEMA 5-15R duplex receptacle is protected by a circuit breaker. This protection is necessary because the UPS is
capable of delivering more than the receptacle’s maximum current rating. The 3000VA model UPS power distribution
plate’s upper two NEMA 5-15R duplex receptacles are protected by a 12 Amp circuit breaker. The lower NEMA 5-15R
duplex receptacle is protected by a 15 Amp circuit breaker. All NEMA 5-15R duplex receptacles on the 5000VA model
UPS are protected by a 15 Amp circuit breaker.

5c. NEMA L6-30R receptacles

Two 30 Amp rated NEMA L6-30R twist-lock outlets provide 208 Vac for large loads.

5d. NEMA L14-30R receptacle circuit breaker

The 3000VA model UPS power distribution plate’s NEMA L14-30R and NEMA 5-15R receptacles are protected by a
two pole, 25 A circuit breaker. The 5000VA model UPS power distribution plate’s NEMA L14-30R is protected by a
two pole, 30 A circuit breaker.

5e. NEMA L14-30R receptacle

The 30 Amp rated NEMA L14-30R receptacle provides a nominal 120/240 Vac output.

6. NEMA L6-30P input plug

The 30 Amp rated input plug has a twist-lock feature to prevent accidental disconnection.