9.9 Typical On-Battery Run Times

Typical On-Battery Run Time Versus Load, 3000 VA Matrix-UPS with SmartCells, in Hours

Number of SmartCells

Computer Load

(VA)

1

2

3

4

5

6

7

8

250

3.07

7.20

11.56

15.93

20.29

24.65

29.02

33.38

500

1.46

3.52

5.80

8.24

10.69

13.13

15.57

18.01

1000

0.57

1.46

2.46

3.52

4.58

5.80

7.02

8.24

1500

0.33

0.83

1.46

2.11

2.81

3.52

4.23

4.99

2000

0.22

0.57

0.99

1.46

1.93

2.46

2.99

3.52

2500

0.17

0.46

0.78

1.18

1.59

1.99

2.45

2.90

3000

0.13

0.36

0.62

0.92

1.25

1.59

1.92

2.30

Recharge Time, in Hours

1.2

2.8

2.7

3.8

4.9

6

7

8.1

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times.
Run times are typical at 25° C (77° F).
Recharge times to 90% of rated capacity after discharge into 50% of rated load.

Typical On-Battery Run Time Versus Load, 3000 VA Matrix-UPS with SmartCell XR Battery Packs, in Hours

Number of SmartCell XR Battery Packs

Computer Load

(VA)

1

2

3

4

5

6

7

8

1000

3

6.75

10.75

14.75

18.75

22.75

26.75

30.75

1500

1.8

4.3

6.9

9.5

12.1

14.7

17.3

19.9

2000

1.2

3

5

7

9

11

13

15

2500

0.9

2.4

4

5.6

7.2

8.8

10.4

12

3000

0.75

1.8

3.25

4.7

6.15

7.6

9.05

10.5

Recharge Time, in Hours

3.8

8.1

12.5

16.9

21.3

25.7

30.1

34.5

Calculations based on loads with a .75 power factor. Lower power factor loads will yield higher run times.
Run times are typical at 25° C (77° F).
Recharge times to 90% of rated capacity after discharge into 50% of rated load.