2.6.5.3 Measurement Type: Interface Level (Loop Control = Interface Level)
Display
Action
Comment
21
SZ Fault
(select)
Select loop current behavior
when level is sensed in safety
zone
Safety Zone is a user-defined area just below the Blocking
Distance. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are None, 3.6 mA,
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)
22
SZ Height
xx.x lu
Enter distance below
BlockDis where SZ Fault will
be asserted
Enter a distance value that develops a safety zone just below the
Blocking Distance. Here the unit will report a Safety Zone Fault
(#21) if the level rises into this area.
23
SZ Alarm Reset
Press Enter to clear a
latched Safety Zone alarm
Clear a latched Safety Zone alarm
24
Threshld
(select)
Select from CFD, Fixed
For interface, refers to threshold for upper level pulse. (Set to
Fixed for most common applications.)
25
IfcThrsh
(select)
Select from CFD, Fixed
Interface mode only. Threshold for interface level pulse. (Set to
CFD for most common applications.)
26
Poll Adr
xx
Enter HART polling address
number (0-63)
Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.
27
Loop Mode
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.
28
Trim Lvl
xx.x lu
Enter value to adjust Level
reading
-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)
29
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
30
Trim 20
xxxx
Fine tune the 20 mA point
Adjust setting to output exactly 20.0 mA on current meter
31
Loop Tst
xx.x mA
Enter a mA Output value
Set mA output to any given value to perform loop test
32
LvlTicks
xxxx
Diagnostic Display
Time of flight from fiducial to interface signal
33
IfcTicks
xxxx
Diagnostic Display
Interface mode only. Time of flight through upper liquid
34
Medium
Diagnostic Display
Interface mode only. Displayed messages are: Unknown,
Oil Only, Thin Oil, Thick Oil, Dry Probe
35
New Pass
xxx
Enter new password (0-255)
Displays encrypted value of present password
36
Language
(select)
Select from English, Spanish,
French, German
Language choice for LCD display. (no HART counterpart)
37
Mdl705HT
Ver3.0a0
Transmitter display
Product identification. Firmware version
38
DispFact
(select)
Select Yes to display factory
parameter menus
Access for viewing the factory parameter
39
History
(current status)
Press Enter to view history
of recent exceptions
Diagnostic Display
40
Run Time
41
History Reset
Press Enter and select yes
to clear history
Similar to SZ Alarm Reset
42
HF cable
(select)
Superuser Parameter
Select from 3-foot or 12-foot remote