Orion Instruments Eclipse 705 User Manual
Page 24
24
57-600 Eclipse
®
Guided Wave Radar Transmitter
2.6.5.2 Measurement Type: Level and Volume (Loop Control = Volume)
Display
Action
Comment
1
*Status*
*Volume*
*% Out *
* Loop *
Transmitter Display
LoopCtrl = Volume
Transmitter default display showing: Status, Volume, % Output
and Loop values cycles every 5 seconds
2
Volume
xxx vu
Transmitter Display
Transmitter displays Volume in selected units
3
% Output
xx.x%
Transmitter Display
Transmitter displays % Output measurement derived from 20 mA
span
4
Loop
xx.xx mA
Transmitter Display
Transmitter displays Loop value (mA)
5
Level
xxx.x 1u
Transmitter Display
Transmitter displays Level Value in selected units
6
PrbModel
(select)
Select the type of probe
used
(Example: 7xR-x)
Select from 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-x, 7xF-E, 7xF-F,
7xF-4, 7xF-P, 7xG-x, 7xJ-x, 7xK-x, 7xL, 7xM, 7xN, 7xP-x, 7xR-x,
7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x as shown on the probe
nameplate
7
PrbMount
(select)
Select the type of probe
mounting
Select from NPT, BSP, or Flange
8
MeasType
(select)
Select type of measurement
Select from Lvl&Vol
9
LvlUnits
(select)
Select level units
Select from cm, inches, feet or meters
10
Probe Ln
xxx.x lu
Enter the exact length of
probe
Probe length is printed on the nameplate and order information
and is the last three digits of the probe model number
11
Lvl Ofst
xxx.x lu
Enter desired Level reading
when probe is dry
Level Offset is the distance from the probe tip to the desired 0
level point (-90 to 300"). Refer to Section 2.6.6
12
VolUnits
(select)
Select the volume units
Select from liters or gallons
13
StrapTbl
nn pnts
Enter to access strapping
table
20-point strapping table enables conversion from level to volume
(Refer to Section 2.6.7 for more information)
14
Dielctrc
(select)
Select range bounding the
dielectric constant of the
media
Select from 1.4–1.7; 1.7–3; 3–10; 10–100
15
Senstvty
xxx
Enter value upward or
downward to sense liquid
surface
Allows fine gain adjustment for single rod probes (this parameter
is password protected for coaxial and twin rod probes)
16
LoopCtrl
(select)
Select variable to control
loop current
Select from Level or Volume
17
Set 4mA
xxxx vu
Enter the PV value for the
4 mA point
A small transition zone (0–6") may exist at the top/bottom of
the probe. See Functional Specifications Probe, Section 3.6.1
18
Set 20mA
xxxx vu
Enter the PV value for the
20 mA point
A small transition zone (0–6") may exist at the top/bottom of
the probe
19
Damping
xx s
Enter time constant of
desired damping
A Damping factor (0–10 seconds) may be added to smooth the
output due to turbulence
20
Fault
(select)
Select the loop current value
in presence of a fault
Select from 3.6 mA, 22 mA or HOLD
21
BlockDis
xx.x lu
Enter distance below refer-
ence point where level is not
sensed
Allows user to ignore level measurements near the top of the
probe