Orion Instruments Eclipse 705 User Manual
Page 25
25
57-600 Eclipse
®
Guided Wave Radar Transmitter
2.6.5.2 Measurement Type: Level and Volume (Loop Control = Volume)
Display
Action
Comment
22
SZ Fault
(select)
Select loop current behavior
when level is sensed in safety
zone
Safety Zone is a user-defined area just below the Blocking
Distance. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are None, 3.6 mA,
22 mA, Latch 3.6 or Latch 22. If Latch 3.6 or Latch 22 is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)
23
SZHeight
xx.x lu
Enter distance below
BlockDis where SZ Fault will
be asserted
Enter a distance value that develops a safety zone just below the
Blocking Distance. Here the unit will report a Safety Zone Fault
(#21) if the level rises into this area.
24
SZ Alarm Reset
Press Enter to clear a
latched Safety Zone alarm
Clear a latched Safety Zone alarm
25
Threshld
(select)
Select the type of threshold
Unit default CFD. Only select Fixed in application with low
dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of Trim
Level may be necessary when threshold is changed)
26
Poll Adr
xx
Enter HART polling address
number (0-63)
Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.
27
Loop Mode
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.
28
Trim Lvl
xx.x lu
Enter value to adjust Level
reading
-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)
29
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
30
Trim 20
xxxx
Fine tune the 20 mA point
Adjust setting to output exactly 20.0 mA on current meter
31
Loop Tst
xx.x mA
Enter a mA Output value
Set mA output to any given value to perform loop test
32
LvlTicks
xxxx
Diagnostic Display
Time of flight from fiducial to level signal
33
New Pass
xxx
Enter new password (0-255)
Displays encrypted value of present password
34
Language
(select)
Select from English, Spanish,
French, German
Language choice for LCD display
35
Mdl705HT
Ver3.0a0
Transmitter display
Product identification Firmware version
36
DispFact
(select)
Select Yes to display factory
parameter menus
Allows for viewing the factory parameters
37
History
(current status)
Press Enter to view history
of recent exceptions
Diagnostic Display
38
HF cable
(select)
Superuser Parameter
Select from 3-foot or 12-foot remote
39
Run Time
40
History Reset
Press Enter and select yes
to clear history
Similar to SZ Alarm Reset
41
FidTicks
xxxx
Diagnostic Display
Time of flight from start of ramp to fiducial
42
Fid Type
(select)
Superuser Password
Select from positive or negative
(Selection only allowed for some probes)
43
Fid Spread