Audible Alarms
Audible Alarm permits the sound of an alarm. It has two options: On or Off.
Use the arrow keys to select an option and press the MENU key to advance
to the Advanced Setup MENU. Refer to Figure 17.
FIGURE 17. ALARM AUDIBLE SCREEN
AUDIBLE ALARM
ON
Advanced Set-Up
1. After pressing the MENU button, the ENTER ADVANCED SETUP screen
will be displayed (refer to Figure 18).
2. The flashing message YES will ask if you want to enter the Advanced
Screen. Press the MENU key as the word YES blinks.
NOTE:
If a change to that selection is not chosen within 3 seconds, the
program will automatically exit the setup mode.
ENTER ADVANCED
SETUP MENU YES
FIGURE 18. ADVANCED SETUP SCREEN
Sensor Calibrate
1. Sensor Calibrate enables the operator to calibrate out sensor error
to give a more accurate reading. Refer to Figure 19. Calibration
offset and PV (actual) temperatures are displayed.
2. To adjust the values in this option, the operator must know how
many degrees off the sensor is. To determine how far off the sensor
is, measure it against a secondary gauge known to be accurate.
3. Once the value is known, adjust the CAL offset value on the screen
using the arrow keys until the displayed temperature matches the
known temperature. Press the MENU key to advance to the Over
temp screen. (Refer to Figure 20.)