Tube Heater General Manual

8

2.0

Safety

Standards, Certifications and Government Regulations

Chart 2.2 •

Standards and Code Installation Guidelines

Building Location

Chart 2.3 •

Standards and Code Installation Guidelines

Building Aspect

Applicable authorities governing the manufacturing or installation of this infrared heater include

(but are not limited to) the following organizations:

• NFPA - National Fire Protection Association.

• ANSI Z83.20b - American National Standards Institute.

• NFPA 54/ANSI Z223.1 - National Fuel Gas Code.

• OSHA - Occupational Safety & Health Administration.

• IAS - International Approval Services.

• AGA - American Gas Association.

• CSA - Canadian Standards Association.

• CE - Certification of Europe.

• IRSC - Infrared Heater Safety Council.

NOTE: Refer to the Series Insert Manual for model specific certifications and approvals.

Building

Location

Guidelines

High

Altitude

Guidelines

Installation of this tube heater is approved, without modifications, for elevations up to
6,000 feet (1,829 m) MSL (sea level) in the United States. Contact the factory for
installations above these elevations.

The type of gas appearing on the nameplate must be the type of gas used. Installation
must comply with national and local codes and requirements of the local gas company.

Non-

Standard

BTU Gas

Guidelines:

Unless otherwise noted on the rating plate, this infrared heater is designed and orificed to
operate on standard BTU gas. Contact the factory if utilizing non-standard BTU gas.

Building

Aspect

Codes and Guidelines

Electrical

The tube heater must be electrically grounded in accordance with the following codes:

United States: Refer to National Electrical Code

®

, ANSI/NFPA 70 (latest edition).

Wiring must conform to the latest edition of National Electrical

Code

®

, local ordinances, and any special diagrams furnished.

Canada: Refer to Canadian Electrical Code CSA C22.1 Part 1 (latest

edition).

Venting

Venting must be installed in accordance with the requirements within this manual and the
following codes:

United States: Refer to NFPA 54/ANSI Z223.1 (latest edition), National Fuel

Gas Code.

Canada: Refer to CAN/CGA B149.1 Installation Codes for Gas Burning

Appliances.