beautypg.com

Detroit Radiant Products Company DET3 Series User Manual

Page 5

background image

5

DET3

Series

1.0

Safety • Clearance to Combustibles

Chart 1.1 •

Clearance to Combustibles in Inches (see Figure 1.1 for Mounting Angles)

When installing the tube heater system, clearances to combustibles for the model tube heater and
configuration must be maintained. Refer to Chart 1.1 below to determine the required distances for your model.

Model Number

Mounting

Angle*

Side

Top

Below

Front

Behind

DET (20, 30, 40) - (65, 75) [N, P] (-3)

9

9

6

60

45°

39

8

10

60

with 1 side shield

29

8

6

60

with 2 side shields

9

9

6

60

20 ft. from burner

7

7

6

30

DET (30, 40) - 100 [N, P] (-3)

14

14

6

66

45°

39

8

10

66

with 1 side shield

29

8

6

66

with 2 side shields

16

16

6

66

20 ft. from burner

7

7

6

30

DET (40, 50) - 125 [N, P] (-3)

20

20

6

76

45°

58

8

10

76

with 1 side shield

42

8

6

76

with 2 side shields

20

20

6

76

20 ft. from burner

7

7

6

30

DET (40, 50, 60) - 150 [N, P] (-3)

24

24

6

81

45°

58

8

10

81

with 1 side shield

42

8

6

81

with 2 side shields

23

23

6

81

20 ft. from burner

11

11

6

44

DET (50, 60) - 175 [N, P] (-3)

34

34

6

92

45°

63

8

10

92

with 1 side shield

50

8

6

92

with 2 side shields

30

30

6

92

20 ft. from burner

11

11

6

44

DET (50, 60) - 200 [N, P] (-3)

41

41

6

94

45°

63

8

10

94

with 1 side shield

54

8

6

94

with 2 side shields

30

30

6

94

20 ft. from burner

11

11

6

44

The stated clearance to combustibles represents a surface temperature of 90ºF (32ºC) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas,
tri-ply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to
assure that adjacent materials are protected from degradation.

Figure 1.1

Mounting Angles

*

Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.

45° Mounting Angle

0° Mounting Angle

with 1 Side Shield

(P/N: SSE)

0° Mounting Angle

with 2 Side Shields

(P/N: SSE)

Front

Behind

Below

Top

Front

Behind

Below

Top

Side

Side

Below

Top

0° Mounting Angle

Side

Side

Below

Top