DET3

Series

4.0

Troubleshooting Guide

Correct wiring or

replace relay.

The blower is faulty

and must be replaced.

Is there 120VAC coming to the

fan from the low fire relay?

Yes

Is the inlet or outlet of

the unit obstructed? i.e.

ice, birds nest, dirt, etc.

Check for loose wiring

or restrictions in hose

connections to the pressure

switch. Are they ok?

Remove obstruction

No

Yes

No

Repair wiring or hose

connections.

No

The heater is equipped with a safety differential

pressure switch. The switch is a normally

open switch and is located in the air chamber.

Temporarilly place a jumper across the terminal of

the switch. Does the igniter spark?

Yes

Replace the pressure switch after verifying the

following:

• Baffle(s) is in the tube farthest from the burner.

• Heater, blower, squirrel cage, intake and

exhaust are clean and free from dirt and

obstructions.

• The 4 in. dia. air intake pipe does not exceed

20 ft. and/or two elbows.

• There is not a negative pressure experienced

at the area of air intake (i.e. attic space, high

winds, very tight buildings, etc.)

If any of the above were occurring, please

address the problem.

Yes

While the switch is

temporarily bypassed,

check for 120VAC from

the switch to the circuit

board. Does 120VAC

enter the circuit board?

No

Replace circuit board.

Faulty wiring.

Repair or

replace wiring.

Yes

No

Key

Start

Question

Process

Question

Corrective

Action

*

*

NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.