DET3

Series

Is the valve switch in

the ON position?

Check that gas pressure is within

minumum and maximum inputs

as indicated on the heater’s rating

plate. Is gas pressure ok?

Does the fan

blower turn on?

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Is the blower

obstructed?

Turn up thermostat.

Is the power at the

heater 120VAC?

No

Remove obstruction

and lubricate blower.

Does the igniter

spark?

Is the igniter

physically

damaged?

No

Yes

Replace igniter.

Yes

No

Find the source of the

electrical problem.

Check the gap on the

igniter. Is the gap between

3/16 in. and 1/4 in.?

No

Adjust gap.

Yes

No

Yes

No

During the ignition

trial, does the gas

valve open?

Yes

Test for 24VAC at the gas

valve during valve opening

(typically 10 seconds after

power to the heater). Is

there 24VAC to the valve?

No

Yes

Is 120VAC being sent

to the transformer?

No

Does the burner light?

Yes

Correct problem.

Replace

gas valve.

Yes

No

Yes

Continued on page 16.

Yes

No

Switch to the ON

position.

Yes

The circuit board and/

or wiring harness

could be faulty. These

should be replaced.

No

No

Yes

Replace 24VAC

transformer.